3 INSTALLATION AND CONNECTION

3.1 CONNECTIONS

Description
Power supply
Controlled voltage
Digital inputs
Relay outputs
CONNECTION INSTRUCTIONS
The electrical connection of the safety relay for other devices is carried out by fixed terminals with screws. To
ensure the electrical connections integrity the following connection instructions must be considered:
ATTENTION!
Ensure that safety relay is turned off before perform the electrical connections. Do not use the safety
relay like supply to external devices.
Table 3.1: Connection descriptions
Type
Pin
IN
A1
AC / DC Positive [+]
IN
A2
AC / DC Negative [-]
OUT
S0
Positive reference [+]
IN
S1
Dual Channel PNP Input
IN
S2
IN
S3
PNP Start Control
13-14
Output Current paths 2
OUT
23-24
NO contacts
Table 3.2: Electrical connection instructions
Parameter
Cable section
Cable resistance
Cable length of control line
Connection type
Tool
Screwdriver slot Nº3
Torque
Installation and Connection
Function
Front View
Value
24 to 12 AWG
0.5 to 2.5 mm²
≤ 40 Ω
≤ 100 m
Screw terminals
≤ 0.4 N.m.
CPW17 | 11