POINT B - SETTINGS
DIP 1 (ON)
BARRIER SLOWSPEEDS ADJUSTMENT IN OPENING AND CLOSING (ON) (See Point C)
DIP 1-2
STORING/ERASING RADIO CODES FOR MOTOR CONTROL (See Point D)
DIP 1-2-3 STORING/ERASING STORING/ERASING for relay R-AUX command (point E)
DIP SWITCHES CONTROL
DIP 4
Single impulse command START and RADIO - step-by-step (ON) - automatic (OFF)
DIP 5
Encoder as safety (ON - enabled)
DIP 6
NORMAL operation (OFF) - PARK operation (ON)
DIP 7
Photocells self-test (ON - enabled)
DIP 8
OPEN 2 command operation in PARK mode
ON - OPEN 2 command is always enabled
OFF - OPEN 2 command works if there is no vehicle on the magnetic sensor connected
to the TLC input (Traffic light control contact opened).
DIP 9
Working after black-out WITH batteries.
ON - The barrier opens and stops in the opening position with the exclusion of all
controls. When the poer supply is back, the barrier closes resetting all controls
OFF - The barrier carries out the normal working until the battery is exhausted.
DIP 10
Operation after black-out WITHOUT batteries.
ON - the boom arm automatically closes if not already closed.
OFF - the boom arm remains still on the point it was when blackout occurred
DIP 11
Enable radio system SUN (ON) - SUN-PRO (OFF)
DIP 12 PRESIDENT 3m (OFF) - PRESIDENT 4m (ON)
LED WARNINGS
DL1
PROG programming activated
DL2
Barrier opening
DL3
Barrier closing
DL4
encoder operation
DL5
manual release microswitch
DL6
STOP command (NC)
DL7
PHOTO 1 contact (NC)
DL8
PHOTO 2 contact (NC)
DL9
TCA - automatic closure time enabled
DL10
Remotes programming enabled
DL11
P1 managed by APP
DL12
PROG and RADIO on MOLEX command
OPEN 1
OPEN 1 command (to enter)
OPEN 2
OPEN 2 command (to exit)
CLOSE
CLOSE command (NO)
START
Single impulse command (NO)
OK CLOSE
Confirmation of closing command
B.I.O
Clock command (NO)
TLC
Magnetic sensor control for traffic light control
ADJUSTMENTS
TRIMMER RUN - High speed regulator
With this trimmer it is possible to adjust the motor speed (standard is set to maximum speed).
TRIMMER LOW SP.OP. and TRIMMER LOW SP.CL. - Slow speed regulators in opening and closing
approach
Slow speed regulation is performed by acting on the LOW SP.OP. and LOW SP.CL. trimmers
through which the output voltage across the motor is varied (turning it clockwise increases
the speed).
The deceleration is automatically determined by the limit switches at about 30° before
reaching the opening or closing limit switch.
TRIMMER TCA - Automatic closing waiting time regulator
standard not enabled and LED DL9 OFF (trimmer rotated completely counter-clockwise)
With this trimmer it is possible to adjust the waiting time before having automatic closing.
The automatic closing is obtained only with the barrier open as a result of the command given
by the opening commands and led DL9 ON (trimmer rotated clockwise to enable the feature).
The pause time can be adjusted from a minimum of 2 s to a maximum of 2 minutes.
R-AUX - AUXILIARY RELAY CONTACT (NO)
By default this relay is set as courtesy light (max 700 W - 3 A- 230 Vac) to operate 3 minutes at
each command, with time renewal at each command.
It is possible to activate the R-AUX contact by remote control by performing the memorization
procedure described in point E and by the RIB GATE App.
POINT C - BARRIER SLOWSPEEDS ADJUSTMENT IN OPENING AND CLOSING
This control is meant to facilitate the installer during the installation of the system, or during
possible further checks.
1 - Set DIP 1 on ON => The led DL1 starts to lighten.
2 - Press and keep pressed the button PROG. (now the movement is carried out with a man
present, open-stop-close-stop-open-etc.) => THE RED LED DL3 switches on and the barrier
closes.
3 - Press and keep pressed the button PROG => THE GREEN LED DL2 switches on and the barrier
opens.
4 - Carry out the calibration of the deceleration speed => set the trimmer LOW SP.OP. and LOW
SP.CL. at the minimum, than press PROG button and keep it pressed => after one second
working the deceleration is activated.
ATTENTION: Verify that the motor has enough power to move the rod both when opening and
closing. Contrariwise, increase the value set on the trimmer until the optimal
condition for working is reached.
ATTENTION: In areas subject to particularly rigid temperatures, rotate the trimmers 5°
clockwise more than the normal value.
5 - At the end of the check set DIP1 back on OFF => The DL1 led switches OFF thus signalling
the exit from the check.
N.B.: During this check the ENCODER and the photoelectric cells are disabled.
E - PROGRAMMING RADIO CODES FOR OPENING (1000 CODES MAX) - with radio
module ACG8069
ATTENTION: before storing the radio codes, use DIP 14 to select which transmitters to use:
DIP 14 OFF: SUN-PRO variable code transmitters can be memorized:
(red)
SUN-PRO 2CH 2-channel - red keys and white led
(green)
SUN-PRO 4CH 4-channel - red keys and white led
(red)
(red)
DIP 14 ON (By factory): You can store transmitters with fixed code SUN:
(red)
SUN 2CH 2-channel - blue keys and white led
(red)
SUN 4CH 4-channel - blue keys and white led
(red)
SUN CLONE 2CH 2-channel - blue keys and yellow led
(red)
SUN CLONE 4CH 4-channel - blue keys and yellow led
(red)
ATTENTION: it is not possible to memorize at the same time transmitters with fixed code and
(red/green)
transmitters with variable code.
(blue)
Programming can be done only when the gate is stationary.
(green)
1 - First set DIP 1 to ON and then DIP 2 to ON. The LED DL12 flashes red for 10 s.
(green)
2 - Press the TRANSMITTER button (usually channel A) within the allotted 10 s. If the remote
(green)
is memorized properly LED DL12 blinks green and a buzzer tone confirms the correct
(green)
memorization. The 10 s for programming the codes are automatically renewed, with LED
(green)
DL12 which flashes red, in order to store the next transmitter.
(green)
3 - To finish programming, wait 10 s, or press the PROG button briefly. LED DL12 stops flashing.
(green)
4 - Re-set DIP 1 to OFF and DIP 2 to OFF.
(green)
ALL RADIO CODES FOR TOTAL OPENING CANCELLATION PROCEDURE
Cancellations can only be performed when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - LED DL12 flashes red for 10 s.
3 - Press and hold the PROG button for 5 s. Memory cancellation is indicated by two green
flashes of LED DL12 and 2 tones of the buzzer.
4 - LED DL12 flashes red again for 10 s and you can add new codes as shown above.
5 - Re-set DIP 1 to OFF and DIP 2 to OFF.
RADIO CODES MEMORY FULL INDICATOR (FOR TOTAL OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The LED DL12 flashes green 6 times when the memory is full (1000 codes). Now LED DL12
blinks red for 10 s enabling possible cancellation of all codes.
3 - Re-set DIP 1 to OFF and DIP 2 to OFF.
F - PROGRAMMING RADIO CODES (FOR R-AUX RELAY) (1000 CODES MAX) - with
radio module ACG8069
* Remote control management can be enabled only by the RIB GATE app.
R-AUX normally works as a courtesy light for 3 minutes.
Through the RIB GATE app it is possible to configure the operation of this relay as desired.
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. DL12 flashes orange for 10 s.
2 - Press the transmitter button (usually channel C) within the allotted 10 s. If the transmitter
is properly memorized LED DL12 blinks green and the buzzer emits a tone. The 10 s are
automatically renewed (DL12 flashes orange) in order to memorize next transmitter.
3 - To finish programming wait 10 s, or press the PROG button briefly. The LED DL12 stops
flashing.
30
cod. ACG6210
cod. ACG6214
cod. ACG6052
cod. ACG6054
cod. ACG6056
cod. ACG6058