ADJUSTING THE PCB
Since the Centralventilation Villa II can be used for different types of central ventilation system and cooker hoods, it may be necessary to adjust
the PCB for the ventilation system and the cooker hood.
The basic ventilation mode can be adjusted in five different steps, but it is important that the basic ventilation is adjusted in accordance with
the minimum voltage that is stated by the motor manufacturer and applicable legislation.
NOTE: If the PCB's output voltage is set too low, it will cause damage to the motor.
ON
DIP
65 volts output to the motor for the basic ventilation mode.
1 2 3 4
ON
DIP
80 volts output to the motor for the basic ventilation mode.
1 2 3 4
ON
DIP
95 volts output to the motor of the basic ventilation mode (default setting).
1 2 3 4
ON
DIP
115 volts output to the motor for the basic ventilation mode.
1 2 3 4
ON
DIP
150 volts output to the motor for the basic ventilation mode.
1 2 3 4
ON
DIP
Basic ventilation mode OFF.
1 2 3 4
ON
DIP
Basic ventilation mode OFF.
1 2 3 4
ON
DIP
Basic ventilation mode OFF. The PCB can be used as a noise filter.
1 2 3 4