Operation Testing
1. Fill unit with water through inlet.
2. Verify that the pump starts when the water reaches 4" – 7" (10.2 cm – 17.8 cm).
3. Verify that the pump stops when the water reaches 1" – 3" (2.5 cm – 7.6 cm).
MAINTENANCE
Risk of bodily injury, electric shock, or equipment damage.
• Before performing any maintenance, shut off water inlet and disconnect power cord from supply
outlet.
• Pump may become hot during operation. Allow pump to cool before servicing.
Refer to
"Replacement Parts" on page 6
while following these instructions. Consult the instruction sheet illustrations for proper assembly and
disassembly of your Little Giant pump.
Cleaning the Basin Screen
1. Remove the four screen cover plate screws, plastic cover plate, seal ring, and screen.
2. Clean inlet screen using a mild detergent and water.
3. Examine O-ring. If deformed, replace.
Cleaning the Basin
1. Remove the screws from cover.
2. Remove the cord grommet. Loosen cords to allow
slack.
3. Remove cover.
4. Remove pump.
5. Clean basin using a mild detergent and water.
6. Reassemble in reverse order.
• Be sure the pump alignment plate's mounting
holes are properly aligned with the locating rib
on the inside of the basin.
• Tighten cover screws to a torque of 18–20 in.-lbs.
Cleaning the Pump
1. Remove pump
2. Pull off the pressed in screen.
3. Remove the six base screws.
4. Remove plastic pump base to clean around impeller and inside base.
IMPORTANT: Do not remove the impeller.
5. Clean parts using a mild detergent and water.
6. Reinstall the base.
• Be sure seal ring is seated properly in groove.
• Tighten screws to a torque of 10–15 in.-lbs.
7. Reinstall the pump screen and pump.
for names and relative location of all components to assist you
MAINTENANCE
Operation Testing
PLATE ALIGNMENT
Monting hole lines
up with locating rib
5