Specifications - Tripp-Lite OmniSmart OMNI500ISO Manual Del Propietário

Ocultar thumbs Ver también para OmniSmart OMNI500ISO:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Specifications

Model
Nominal Voltage and
Input Range
Nominal Input Frequency
and Tolerance
Nominal Output Voltage
Nominal Output
Frequency
Output Voltage Regula-
tion in Line Mode
Output Voltage Regula-
tion in Battery Mode
Nominal Output Power
in W / VA
Output Voltage Waveform
Maximum Output
Current @ P . F.
Efficiency with
Nominal Load
Maximum Operating
Altitude at 100% of
Nominal Power
Online Overload
Capability
Overload Capacity in
Battery Mode
Autonomy Time at
Full Load
Battery Recharge Time
Transfer Time
Outlets
Maximum Input Current
20-08-276 932490.indb 8
20-08-276 932490.indb 8
OMNI500ISO
OMNI700ISO
120V~, 81-143V
120V~, 81-143V
60 Hz (+/- 5 Hz)
60 Hz (+/- 5 Hz)
120V~ in line mode
120V~ in line mode
and 115V~ battery
and 115V~ battery
60 Hz (+/- 0.5 Hz)
60 Hz (+/- 0.5 Hz)
120V~ (+8% / -18%)
120V~ (+8% / -18%)
115V~ (+/- 5%)
115V~ (+/- 5%)
300W / 500VA
500W / 750VA
Sinusoidal in line mode
Sinusoidal in line mode
and quasi-sine (PWM)
and quasi-sine (PWM)
in battery mode
in battery mode
4.2A @ 120V~
4.2A @ 120V~
91%
91%
6562 ft.
6562 ft.
(2000 m)
(2000 m)
125% @ 10 minutes
125% @ 10 minutes
110% +/- 10% @ 5
110% +/- 10% @ 5
seconds
seconds
5.4 minutes @ 300W
13.5 minutes @ 500W
4.5 hours
4.5 hours
6 milliseconds typical
(10 milliseconds max.)
(10 milliseconds max.)
3x 5-15R outlets
6x 5-15R outlets
with battery backup,
with battery backup,
regulation and surge
regulation and surge
protection
protection
4.8A
5.5A
8
OMNI1000ISO
120V~, 81-143V
60 Hz (+/- 5 Hz)
120V~ in line mode
and 115V~ battery
60 Hz (+/- 0.5 Hz)
120V~ (+8% / -18%)
115V~ (+/- 5%)
700W / 1000VA
Sinusoidal in line mode
and quasi-sine (PWM)
in battery mode
5.8A @ 120V~
91%
6562 ft.
(2000 m)
125% @ 10 minutes
110% +/- 10% @ 5
seconds
8 minutes @ 700W
4.5 hours
6 milliseconds typical
6 milliseconds typical
(10 milliseconds max.)
6x 5-15R outlets
with battery backup,
regulation and surge
protection
7.6A
3/5/2021 1:18:21 PM
3/5/2021 1:18:21 PM
Tabla de contenido
loading

Este manual también es adecuado para:

Omnismart omni700isoOmnismart omni1000iso

Tabla de contenido