Refrigerant Gas Recovery & Containment - Promax RG6000-E Manual De Instrucciones

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 89
Advanced Test Products Europe
RECOVERY & CONTAINMENT
Safety comes first. Read all safety information for the safe handling of refrigerant
including the Material Safety Data Sheet provided by your refrigerant supplier. Never
operate unit in an explosive environment. Wear safety glasses and protective gloves.
Work area must be well ventilated. This unit should only be operated by a qualified
technician.
*** CAUTION: REFRIGERANT STORE CONTAINERS ***
Use only approved cylinders with a minimum of 41 bar (595PSI) working pressure that
serve the current regulations.
NOTE: Recovery cylinders are designed for different pressures. Do not exceed the
working pressure of each cylinder.
Safety codes recommend that closed tanks not be filled over 80% of volume with liquid.
The remaining 20% is called head pressure room.
NEVER TRANSPORT AN OVERFILLED CYLINDER.
Refrigerant expands when it gets warm and may cause a tank to explode if overfilled.
CYLINDER TEMP.
STARTING WITH
CYLINDER 80%
FULL BY VOLUME
SPACE OCCUPIED
BY LIQUID
STARTING WITH
CYLINDER 90%
FULL BY VOLUME
SPACE OCCUPIED
BY LIQUID
REFRIGERANT GAS
16 °C
21 °C
80 %
81%
90%
92%
38 °C
83%
96%
2
RG6000-E
54 °C
66 °C
90%
94%
100%
Tabla de contenido
loading

Tabla de contenido