Installation site selection - Indoor unit
AVOID
• Direct sunlight.
• Nearby heat sources that may affect unit performance.
• Areas where leakage of flammable gas may be expected.
• Locations where large amounts of oil mist may occur
(such as in kitchen or near factory equipment) because
oil contamination can cause operation problems and may
deform plastic surfaces and parts of the unit.
• Unsteady locations that will cause noise or possible water
leakage.
• Locations where the indoor unit and the remote control unit
will be splashed with water or affected by dampness or
humidity (i.e. in laundries).
• To make holes in areas where electrical wiring or conduits
are located.
DO
• Select an appropriate position from which every corner of
the room can be uniformily cooled.
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with
l
foamed polyethylene (min. thickness 8mm).
MODEL
OUTER DIAMETER
GR9FI30 / 40
6,35 mm
6,35 mm
GR9FI50
PVC pipe for condensate drain pipe (ø int.18mm) in lenght suitable to let the condensate flow into the outside drainage.
l
Anti-freeze oil for flare connections (about 30g).
l
Electric wire: use insulated copper wires of size and length as shown at paragraph "WIRING DIAGRAMS".
l
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
TOTAL TUBING LENGHT
AT SHIPMENT (m)
7,5
REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT
For tubing 1/4 " - 3/8" = 15g/m
For tubing 1/4 " - 1/2" = 20g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H)
No additional charge of compressor oil is necessary.
NARROW TUBE
MIN. THICKNESS
0,8 mm
0,8 mm
H
TOTAL TUBING LENGHT
WITH ADDITIONAL REFRIGERANT (m)
• Select a sufficiently strong location to support the weight
of the unit.
• Select a location where tubing and drain hose have the
shortest run to the outside.
• Allow access for operation and maintenance as well as
unrestricted air flow around the unit.
Installation site selection - Outdoor unit
AVOID
• Heat sources, exhaust fans.
• Direct sunlight.
• Damp, humid or uneven locations.
• To make holes in areas where electrical wiring or conduits
are located.
DO
• Choose places as cool as possible and well ventilated.
• use lug bolts or equal to bolt down the unit, reducing
vibration and noise.
LARGE TUBE
OUTER DIAMETER
9,52 mm
12,7 mm
15
3
MIN. THICKNESS
0,8 mm
0,8 mm
H
(go on page 4)
EG