Remote Control Pro - Schüco 1600 Pro Manual Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 36
3.4
Connecting panel
Abb. 3.4: Conection panel
Battery +
Battery cable Plus
(already installed)
Battery -
Battery cable minus
(already installed)
16A
16A Protection switch for the
Protection
Transfer system
AC Output
AC-output clamp
AC Input
AC-input clamp
Relais
Temp.
Connecting terminal for
Temperature sensor
Equalize
Slide switch for equalization of
the Battery
Transfer delay Slide switch for Transfer Delay
Remote contr. Connecting terminal for the

Remote Control Pro

Caution!
Before connection the battery, check the
polarity (+/-) !
Wrong connection can destroy the Inverter
1600 Pro!
3.5
Cabling/wiring
Connecting of the Inverter 1600 Pro is a very important
step in the installation. You must take care that all
connecting work is carried out in a clean and correct
manner and that under no circumstance a cable is
connected to a wrong terminal.
26
Connecting of the Inverter 1600 Pro must
be carried out in the following order. In case
of dismantling this order must be reversed.
3.5.1 Pre-installation settings
Before you start with the cabling of the Inverter 1600 Pro
you must set the type of battery. In case that sealed-
gel batteries are used then you must set the small
slide-switch „Equalize"
the connecting terminals, to OFF position. In case of
„normal" lead-acid batteries, these can handle a higher
equalizing charge, the same slide switch can be set to
ON position. In case of doubt leave the setting in OFF
position.
3.5.2 Connection the battery
Get the batteries ready for connection: matching battery
terminals, matching fuse on a clamp. Prepare battery
cables, if necessary press on cable tabs/shoes. Connect
red cable on Plus (+) pole and the black cable on the
Minus (-) pole. On connecting the second cable to the
battery pole a spark is produced, because for a short
time high current fl ows into the Inverter 1600 Pro to
charge the capacitors. For this reason follow strictly the
safety measures described in this manual. Check if the
red LED OFF
is lit. If not, press shortly on the switch
ON/OFF
, now OFF should be lit.
On connecting the battery the Inverter 1600 Pro needs
1 – 2 Minutes to calculate the actual ca-pacity of the
battery. During this time the battery condition is shown
as 100% charged. (LED 15 lit).
If the LED
Battery Low/High is lit, the battery charge
is too low. If the LED
the battery charge is too high.
Caution!
With a wrong battery voltage the Inverter
1600 Pro can be destroyed.
(For example: connecting to a 48V-Battery).
Nevertheless if the Inverter 1600 Pro had been
connected with reverse polarity, it is highly probable that
the fuse inside the casing is broken. Before opening
the casing cover all terminals must be disconnected
including the battery.
If the Inverter 1600 Pro does not function after the
change of the fuse and correction of the polarity, it
means that it is broken and must be sent for repair.
231 575
which is on the front with
Battery Low/High is blinking,
02.2008
Tabla de contenido
loading

Tabla de contenido