EN
CHARACTERISTICS
Supply voltage
Power Supply
Max. current
Operating temperature
Material of housing
Housing dimensions (h,Ø)
Weight
Protection class
Degree of protection
Conformity
ACCES-
Mast Adaptor
SORIES
Ref. 1860321
Dimensions
H: 90 mm/Ø 25 - 50 mm H: 1 m/Ø 50 mm 200 x 90 x 30 mm (w x d x h)
SENSORS
M8
Wind speed
●
Wind direc-
tion
Brightness
● (x4) ● (x8) 0...100 kLux
Temperature ●
Precipitation ●
*) Sensor dry, bedewing protection: 0.1 W / Sensor wet, drying phase: 1.1 W
CABLES
Connection to ...
Power Supply
RS485 Bus
24 V DC + 10 % / - 30 %
Mandatory use of certified power supply with limited power (certified accord-
ing to the relevant version of 60950-1 or 62368-1, EN/IEC or UL as needed in
the country of use). Limited power classified as LPS, PS2 or UL class II (accord-
ing to standard).
230 mA@24 V
- 30° C ... + 70° C
Polycarbonate
105 mm, 103 mm
162 g
III
IP 44 in working position
www.somfy.com/ce
Metallic Mast
Ref. 1860335
1
M13
Measuring Range
●
0...35 m/s
●
1...360°
●
- 30...+ 50° C
●
1/0
(precipitation yes/no)
Cable
Min.: 2 x 0.28 mm²/22 AWG
Max.: 2 x 0.5 mm²/20 AWG
Min.: 2 x 0.28 mm²/22 AWG
Max.: 2 x 0.5 mm²/20 AWG
Wall Mount Bracket
Ref. 1860336
2
Resolution Accuracy
0.1 m/s
± 5 % (± 1 m/s) rms over 360 °C
1°
± 5° with laminar flow and wind speed > 2 m/s
0.1 kLux
± 200 Lux with < 2kLux; ± 10 % with ≥ 2 kLux
0.1° C
± 1° C with laminar flow and windspeed > 2 m/s
Thermal
output *)
Twisted pair
-
Required
animeo IB+/IP/KNX Weather Station M8/Weather Station M13 Ref. 5146655D
Bracket
Ref. 1860320
3
180 x 80 x 80 mm
Max. length
-
500 m/1,640 ft
4
- 11/32