A-2. Installation Instruction for the "Connecting Cord" (SPX-WDC5): Malfunction signal side
1. Open the front cover and electrical cover of indoor unit.
2. Connect (1) 11 pin connector to CN6 of indoor main PWB.
3. Join (3) Malfunction signal connector to the HA-ADAPTER(HA-S100TSA: optional part).
4. Join the LED circuit(Local procurement) to "3" & "4" of HA-ADAPTER
5. Make sure not to clamp any wire when reassemble the electrical cover.
6. Reassemble the front cover and do an operation check after malfunction signal has been connected.
MAIN PWB
Joint the cord from Dry Contact Cord to [Connecting Cord (SPX-WDC5)]
by using [Contact with sleeve].
4 YELLOW
3 ORANGE
2 RED
1 BROWN
HA ADAPTER (HA-S100TSA)
*Specification of the LED circuit : (a) Power supply : DC 5V to 24V, (b) Current : 10mA or less
NOTES: When a failure occurs, a malfunction signal is output and LED is turned on.
All manuals and user guides at all-guides.com
(1) 11 pin connector
(2) DRY CONTACT side
HA ADAPTER (HA-S100TSA)
(3) MALFUNCTION SIGNAL side
SPX-WDC5 CONNECTION DIAGRAM
HA-S100TSA CONNECTION DIAGRAM
– 3 –
CONTACT WITH SLEEVE
DRY CONTACT CORD
LED
This circuit is local procurement