Unit Operation Modes; Plc Messages; Status Messages - Nederman FlexPAK 800 Manual Del Usuario

Ocultar thumbs Ver también para FlexPAK 800:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 152
EN
FlexPAK 800/1000 DX
4.
The unit starts when the test start button is pressed, Figure 7, item 7, or when a valve is
opened at a workstation.
Always switch off the unit at the end of the shift by pressing the Standby/Running button on the
control panel, or use the weekly timer, see Section '7.2.2 Weekly timer'.
5.3.2

Unit operation modes

FlexPAK 800/1000 has the following four operation modes:
1.
Off mode
2.
Standby mode
3.
Running mode
4.
Idling mode
See Section '6.1 Status messages' for more information about each mode.
How the unit moves from one operation mode to another is explained below. See also Figure 23
for a flow chart showing how the unit goes through its four different operation modes.
As discussed in Section '5.3.1 Starting the unit', when the unit is in Off mode, the unit can be
put into Standby mode with its motor off and the Filter Cleaning Valve (FCV) closed by pressing
the Standby/Running button. While the unit is in Standby mode, the unit can be put back into Off
mode again by pressing the Standby/Running button.
The unit goes from Standby mode into Running mode when it receives a pilot signal by a valve
being opened at one or more work stations (in other words, someone starts to work). The unit's
motor is now on and the FCV is closed. The DIR_Time and SSR_Time timers are not started, see
Sections '7.2.4 DIR_Time' and '7.2.5 SSR_Time'.
The unit stays in Running mode as long as there is an active pilot signal. However, the unit can
still be put into Off mode by pressing the Standby/Running button.
Note that if only one workstation is connected to the unit, or if only one work station is in use
and work stops at that one station, the pilot signal stops. If there is more than one work station
connected to the unit, and more than one work station is in use, the pilot signal only stops if work
stops at all workstations (in other words, all valves close).
When the pilot signal stops, the DIR and SSR timers start. If work resumes at one or more work
stations within 10 seconds, the unit stays in Running mode. The DIR and SSR timers are reset
back to zero and are stopped.
If DIR_Time is set for 10 seconds (default), and the pause in work is longer than 10 seconds, DIR_
Time elapses. The unit then goes into Idling mode with its motor on and the FCV open.
If a new pilot signal is sent within 12 minutes, the unit goes back into Running mode. The DIR and
SSR timers are again reset to zero and are stopped. However, if SSR_Time is set for 12 minutes,
which is the default setting, and there is no new pilot signal within 12 minutes, SSR_Time also
elapses.
The unit then goes into Standby mode until it either receives a new pilot signal that puts the unit
back into Running mode, or the unit is turned off (in other words, put into Off mode) by the
weekly timer, see '7.2.2 Weekly timer', or by pressing the Standby/Running button.
6

PLC messages

The following sections show the different status, warning and alarm messages that can be seen in
the PLC display.
6.1

Status messages

The following status messages give information about what mode the unit is in or what routine
service is being performed.
32
All manuals and user guides at all-guides.com
loading

Este manual también es adecuado para:

Flexpak 1000