Product Information on
PROFIBUS bus connector
RS 485-IS; 6ES7972-0DA60-0XA0
A5E00335524-03
Application area
The RS 485-IS PROFIBUS bus connector may only be
used to connect the following devices:
ET 200iSP distributed I/O
Approved devices in accordance with: PROFIBUS RS
485-IS User and Installation Guideline
(http://www.profibus.com).
Additional information
Additional information on the RS 485-IS PROFIBUS
connector is provided in the ET 200iSP Distributed I/O
manual (6ES7152-1AA00-8BA0).
This manual can be requested from a Siemens
representative in an office in your area, or free of charge
on the Internet at:
http://www.siemens.com/automation/service&support
Maintenance
The RS-485-IS PROFIBUS bus connector is
maintenance free. To have it repaired, send the bus
connector to the following address:
Siemens AG, Elektronikwerk,
Werner-von-Siemens-Str. 50, D-92224 Amberg
The bus connector may only be repaired at this address!
Certification
CENELEC
II 2 G and I M2
Ex ib IIC T4; Ex ib I
KEMA 04 ATEX 1233
IECEx KEM 05.0015
Note
The RS 485-IS PROFIBUS bus connector of device
category 2G may be used in zone 1 hazardous
areas.
Technical data
Module-specific data
Interface
Connectable terminating resistance integrated
Voltages, currents, potentials
Electrical isolation
• between cable shield and electronics yes
Insulation tested with
Safety-related data
U
= V
i
max
I
= I
i
sc
L
, C
i
i
T
A
Note
Make sure that a protection class of IP 20 (in
accordance with EN 60529) is ensured even when
the RS 485-IS bus connector has been
disconnected!
© Siemens AG 2006
CE
RS 485-IS
AC 500 V
=
±4.2 V
=
4.8 A
0 (negligible)
=
-25 to +70 °C
41.2 +/-2.5
0344
Bus cable installation
(1)
Cable shield
(2)
Bus cable (e.g. 6XV1 830-0EH10)
- strip insulation, e.g. with stripping tool
6GK1905-6AA00
(3)
Contact cover for insulation-piercing connecting
device
- insert the green and red cores into the open
contact cover right up to the end
- close the contact cover (press it down as tight as
possible)
(4)
Insert the cable into the opening (cable shield
must lie bare on the metal guide)
(5)
Close the housing cover and screw it shut
Note: The bus cables are connected by means of an
insulation piercing technique (Fast Connect connection
system). The insulation piercing connecting devices are
designed for 10 connecting cycles.
If you wish to reconnect a line that has already been
connected, you must crop it first.
Bus connection for the first and last node on
PROFIBUS
Cable must always be connected on the left (see label
A1, B1)
Switch position must be "ON" for the first and last node
on the PROFIBUS.
(terminating resistance connected).
Bus connection for all other nodes on PROFIBUS
Cable feed must always be connected on the left (see
label A1, B1). Cable extension must always be
connected on the right (see label A2, B2).
Switch position must be "OFF" for all other nodes on the
PROFIBUS.
(terminating resistance disconnected).
A1 B1
A2 B2
7.5 +1