5.5.5 Label from the terminal board cover (inside)
Read the manual !
Bedienanweisung lesen !
SPC m1/V1.0
11.06.2015
1
2
3
4
5
sensor
sensor
system
vessel
pressure
pressure
27 28 29 30
31 32 33 34 35 36 37
RS232
switch
switch
level
pressure
Terminal
Explanation of the abbreviations on the label on the terminal board cover.
Note: The switch settings shown represent the current-free, non-switched state.
FU/FC
Frequency converter
refill IN 230V
Top-up signal input 230V
extra-low voltage
Protective low voltage
fault
Fault, common fault output
M
Motor (pump motor)
high voltage
Voltage as per markings
L
Phase
N
Neutral wire
PE
Protective earth (PE) conductor
mains supply
Power feed
NO
normally open (volt-free in open position)
NC
normally closed (volt-free in closed position)
pwm
Input for water meter with pulse output (option)
sensor
Sensor
system pressure
System pressure sensor input
vessel pressure
Vessel pressure sensor input
temperature
Temperature sensor input
FC out
FC out
ohmic load
Ohmic load, resistance
motor ball valve
Motor ball valve
level switch
Level switch / float switch / dry run protection
pressure switch
Pressure switch controlled degassing
refill
Top-up
release FC
release FC
standby
standby
mains supply
Mains feed
GND/AGND/GNDA
Mass (A=analogue, only connected as per terminal diagram)
out analogue
out analogue
ATTENTION:
Even if unit is isolated from
power supply, terminals 12,
13, 14, 16 and 17 may carry
230V voltage!
NO
NC
6
7
8
9
10 11
12 13 14
fault
5A
30
VDC
5A
250
VAC
ohmic load
analog
sensor
counter
out
FC OUT
pwm
temperature
4 - 20 mA
option
option
38 39 40
FC
0 - 10 V
release
OUT
refill
out
analog
option
ACHTUNG:
Trotz Netztrennung kann, an
den Klemmen: 12, 13, 14, 16
und 17 eine Spannung von
230V anliegen !
15
16 17
18
19 20
21
22 23
24
PE
N
L
PE
~
signal in
refill IN 230V
FU/ FC
41
42 43
44
45 46
47
48 49
50
PE
N
L
PE
230V 50/60Hz
motor ball valve
mains supply
Klemmenplan Vacumat ECO 20150708
25 26
N
L
FC
M
51 52
N
L
15