7
Technical data
Input data
Measuring principle
Measured value
Voltage measurement V1, V2, V3, U1, U2, U3
Input voltage range (direct)
Phase/phase
Phase/neutral conductor
Input voltage (via external transformers)
Primary
Secondary
Power consumption, voltage input
Surge voltage (permanent)
Accuracy
Current measurement I1, I2, I3
Input current (via external transformers)
Primary
Secondary
Overload capacity
Short-term overload
Power consumption, current input
Discrimination threshold of measuring range nominal
value
Measuring range
Accuracy
Power measurement
Measuring range
Accuracy
Real energy (IEC 62053-22)
Reactive energy (IEC 62053-23)
Output data
Optional for special function/communication module
Supply
Supply voltage range
Nominal power consumption
104513_en_03
True r.m.s. value measurement (TRMS) up to
63Harmonic
AC sine (50/60 Hz)
18 .... 700 V AC
11 .... 404 V AC
500 kV AC
60, 100, 110, 115, 120, 173,190 V AC
≤ 0.1 VA
760 V AC
0.2 %
10 kA
1 A or 5 A
6 A (max.)
10 I
for 1 s
n
≤ 0.1 VA
10 mA
0 ... 11 kA
0.2 %
0 ... 8000 MW/Mvar/MVA
0.5 %
Class 0.5 S
Class 2
110 ... 400 V AC ±10 % (2901366)
120 ... 350 V DC ±20 % (2901366)
12 ... 48 V DC -6 %/+20 % (2902352)
< 10 VA (without extension modules)
< 20 VA (with extension modules)
English