ELECTRICAL CONNECTION
• Before connecting the appliance make sure that the voltage and frequency rated on the data plate conform
to those of the mains supply.
WARNING! A double pole trip switch with a least 3 mm between the contacts must be installed between the
unit and the mains supply.
• Connect the control and security device wires.
• Connect the power supply cable to the device.
• Do not use cables with aluminium conductors; do not solder the ends of cables which are to be inserted into
the binding posts; use cables which are marked T min 85°C and are resistant to atmospheric agents.
• The terminal wires must be positioned in such a way that both the wire and the insulating sheath are tightly
fastened (plastic binding is sufficient).
Terminal board connections
1-2
Power supply/motor earth binding posts
3-4
Programmer power supply 230 Vac
5-6-7
Motor command output Closing-Opening-Common
8-9
Courtesy light output 230 Vac 300 W
10-11
Warning lights output 24 Vac 8 W
24 Vac 7 W output, powering external devices
12-13
14
TA (NO) opening button input
15
TC (NO) closing button input
CMN common for all inputs and outputs
16-17
TB (NC) blocking button input
18
FTC (NC) security device input ( inverting photocells during closing). The opening of this contact will
19
provoke a travel direction inversion during closure due to the cutting in of the safety device.
20
CSP (NC/8.2 kΩ) safety edge input. Opening this contact will provoke a travel direction inversion during
the closing stage and block movement during the opening stage (movement will continue the next time
a command is given).
21
CSP_DIS (NO) safety edge disable input (CSP and CSPF). Closing this contact will disable the safety edge
(only used in the last stage of the closing cycle in order to make sure that the travel limit is reached).
22
Mass for radio receiver antenna
23
Radio receiver antenna pole
24
0 Vdc output digital safety edge power supply
12 Vdc output digital safety edge power supply
25
26
CSPF digital safety edge signal input
ALL UNUSED NC CONTACTS MUST BE BRIDGED
Power up the circuit and make sure that the indicator LEDs are in the following condition:
- L1
Green power on LED
- L2
Red time programming LED
- L3
Red transmitter code management LED
- L4
Blocking button LED "TB"
- L5
Photoelectric cell indicator LED "FTC"
- L6
Safety edge indicator LED "CSP"
- L7
Safety edge indicator LED "CSPF"
The led is OFF if the safety device is active
(1)
If the digital safety edge is not used open jumper J2 (Led L7 remains OFF)
(2)
If the green power on LED "L1" does not light up check the condition of the fuses and the power cable contacts
at binding posts 3-4 (fig.1).
11
ON
OFF
OFF
ON
(1)
ON
(1)
ON
(1)
ON
(1,2)