SMA Sunny Tripower 8000TL Manual De Instrucciones página 22

Ocultar thumbs Ver también para Sunny Tripower 8000TL:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 127
5 Disconnecting the Inverter from Voltage Sources
20. Remove all screws from the upper enclosure lid (hex socket, AF 4).
21. Pull the upper enclosure lid forward to remove it.
22.
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the inverter through
electrostatic discharge.
• Ground yourself before touching any component.
23. Discharge the DC link in the following order. For this purpose use, for example, a 2-pole
voltage detector that does not have its own voltage source.
• Contact point DC+ and contact point DC- to
0 V
• Contact point DC+ and contact point
grounding conductor (PE) to 0 V
(threaded hole for 1 lid screw)
• Contact point DC- and contact point grounding conductor (PE) to 0 V
(threaded hole for 1 lid screw)
22
STP8-17-STP15-20TLEE-AC-CON-RM-xx-10
NOTICE
DC+
SMA Solar Technology AG
DC−
PE
Replacement Manual
Tabla de contenido
loading

Tabla de contenido