Vortice VORT HR 300 NETI Manual De Instrucciones página 40

Ocultar thumbs Ver también para VORT HR 300 NETI:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 96
ENGLISH
From this new page you can manage:
• Mot. Spd.
To set MIN and MAX speed on the 2 fans.
• Setp Byp
"Bypass" mode activates based on the temperature:
"Setp Byp" is selectable in a range between 15°C and 30°C
(default 18°C).
• No Frost
Select "No Frost" from the Installer "Operations menu" to
access the "No Frost Menu." From here you can choose the
functions that can be activated during the "No Frost" procedure.
For further details on how to select functions:
See: "Installer Operations Menu", "No Frost Menu".
• Lifetime
To set the filter duration time, which can vary between 3, 6 and
12 months.
• Language
Language selection
• Modbus ID
IIn the presence of another installed remote HMI user interface,
you can configure a different address than the default one
(which is "160"). (pag 40)
• Comm add
It is the variable that defines the Slave modbus address. The
default value, which can be changed from 001 to 254, is 1.
• Comm par
It is the variable that defines the Slave modbus Baud Rate. The
default value, editable in 9600, is 19200.
40
FAN SPEED
FAN1
FAN1
FAN2
FAN2
SETP BYP
018
NO FROST
UN - BALAN.
UN - BALAN.
HEATER
HEATER FORC
LIFETIME
012
LANGUAGE
ITA
MBUS ID
160
COMM ADD
001
COMM PAR
N 19200
[ ▲ ]
MIN
MAX
MIN
MAX
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]

Hide quick links:

Tabla de contenido
loading

Tabla de contenido