Enclosure:
Configuration notes for in-line fuse switch-disconnectors 3NJ6
Within the scope of the configuration, a blanking cover is automatically positioned at the top of the device compartment, which, however, does not
reduce the effective device compartment of 1750 mm or 1550 mm.
Configuration rule for ventilated sections with plug-in 3NJ6 switch disconnectors:
If these notes are not observed, premature aging of fuses and uncontrolled release may occur as a result of the local overheating. All data refer
to ambient temperatures of the power distribution board of 35 °C as a 24 h average.
Conversion factors for other ambient temperatures:
Ambient temperature of the power
distribution board [°C]
Conversion factor
Method 1: Summation current of all feeders in the section  2000 A
Operating current of the
fuse links:
Disconnector arrangement:
Permissible current
(continuous operating
current at an ambient
temperature of
35 °C)
Disconnectors size 3
 440 A to 500 A
(group formation not
of the individual device
permissible)
< 440 A
of the individual device
Disconnectors size 2
 320 A
(group formation not
of the individual device
permissible)
Disconnector groups size
 400 A
00 and 1
= summation current of
the fuse links group x 0.8
* below the last strap in the section there are 100 mm blanking cover instead of 50 mm resp. instead of 50 mm blanking cover no ones needed
8PQ9800-7AA82
20
25
30
35
1.1
1.07
1.04
1.00
0.8 x I
of the fuse
N
Installed in the section from the bottom to the top, descending from size 3 to size
00
Arrangement of disconnectors and blanking covers
200 mm = each 100 mm blanking cover
above and below *
150 mm = each 50 mm blanking cover
above and below *
50 mm = each 50 mm blanking cover
below *
100 mm = each 100mm blanking cover
below * per group
40
45
50
55
0.95
0.9
0.85
0.8
A1