Section 2
Pumping Capacity
Positive Displacement Pump P 1/P 2
Magnetic Drive Pumps MD 1/MD 2
Pumping Capacity
Turbine Pump T 1/ T 5
2-6
ThermoFlex
Bar
PSIG
7
100
6
80
5
60
4
3
40
2
20
1
0
5
1
Bar
PSID
7
100
6
80
5
60
4
3
40
2
20
1
2
• Pump curves are nominal values. Pressure values for turbine pumps are differential pressures
between the inlet and the outlet of the chiller.
• Pump performance results were obtained with no restrictions on the return to the system or with
any options installed. For example, utilizing the DI option will result in a 0.5 gpm flow reduction.
• Specifications obtained at sea level using water as the recirculating fluid, at a 20°C process
setpoint, 25°C ambient condition, at nominal operating voltage. Other fluids, fluid temperatures,
ambient temperatures, altitude or operating voltages will affect performance. See Section 3.
• Thermo Fisher Scientific reserves the right to change specifications without notice.
C
B
D
10
15
2
3
4
Flow Rate
A
C
D
10
20
4
6
Flow Rate
A: P 2/MD 2, 60 Hz
B: P 2/MD 2, 50 Hz
C: P 1/MD 1, 60 Hz
D: P 1/MD 1, 50 Hz
A
20
LPM
5
GPM
A: T 5, 60 Hz
B: T 5, 50 Hz
C: T 1, 60 Hz
D: T 1, 50 Hz
B
30
40
8
10
12 GPM
Thermo Scientific
LPM
Tabla de contenido
loading