Designation
Analog output device
4 AO U/I 4×M12
IO-Link master
4 IO-L + 8 DI + 4 DO DC 24V/1,3A 8×M12
4 IO-L 4×M12
Approval
ATEX approval
According to EN 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part 15: Type of protection "n"),
EN 60079-0 (Electrical apparatus for potentially explosive gas atmospheres - Part 0: General Requirements) and EN 60079-31
(Equipment dust ignition protection by enclosure "t").
II 3 G Ex nA IIC T4 Gc
II 3 D Ex tc IIIC T90°C Dc
DEKRA 12ATEX0220 X
OR
According to EN 60079-7 (Electrical apparatus for potentially explosive atmospheres - Part 7: Increased safety "e"),
EN IEC 60079-0 (Electrical apparatus for potentially explosive gas atmospheres - Part 0: General Requirements) and
EN 60079-31 (Electrical apparatus for potentially explosive atmospheres – Part 31: dust ignition protection by enclosure "t").
II 3 G Ex ec IIC T4 Gc
II 3 D Ex tc IIIC T90°C Dc
DEKRA 20ATEX0119 X
Special conditions in hazardous areas:
Install the device in a way that risk of mechanical danger is low.
To avoid electrostatic charging wipe the enclosure surface with a wet cloth only.
Use the device only in an environment where it is protected from UV light.
The following additional conditions apply for use in an area which requires the use of devices with EPL Gc:
•
Use the device only in an area up to Pollution degree 2 according to EN 60664-1.
•
Provisions must be taken to prevent the rated voltage from being exceeded by transient disturbance voltages of more
than 119 V.
IECEx approval
According to IEC 60079-7 (Electrical apparatus for potentially explosive atmospheres - Part 7: Increased safety "e"),
IEC 60079-0 (Electrical apparatus for potentially explosive gas atmospheres - Part 0: General Requirements) and IEC 60079-31
(Electrical apparatus for potentially explosive atmospheres – Part 31: dust ignition protection by enclosure "t").
II 3 G Ex ec IIC T4 Gc
II 3 D Ex tc IIIC T90°C Dc
IECEx DEK 20.0070 X
6
Article number
6ES7145-6HD00-0AB0
6ES7148-6JA00-0AB0
6ES7148-6JD00-0AB0
Use of the ET 200eco PN in zone 2/zone 22 hazardous areas
A5E03879075-AB, 02/2021