For information on making claims under the terms of the warranty, please go to
www.steinel-professional.de/garantie
If you have a warranty claim or would like to ask any question regarding your
product, you are welcome to call us at any time on our Service Hotline
01733 366700.
5
Y E A R
MANUFACTURER'S
WARRANTY
10. Technical specifications
Dimensions (Ø × D)
Ø 80 × 20.5 mm
Power consumption
4 mA / 2-DALI users,
12-22.5 V
Sensor technology
Passive infrared (IR)
DALI interface
DALI control line (multi-master capability
for communication with the DALI Application
Controller/DALI sensor), DALI start-up time < 1 s
Detection zone
360° for a 90° angle of aperture
(84 detection beams and 168 detection zones)
Light measurement
2-1000 Lux
Reach
4 × 4 m presence, radial,
6 × 6 m tangential / 2.8 m height
IP rating
IP20
Temperature range
0°C to + 40°C
, no SELV
- 18 -
11. Troubleshooting
Malfunction
Cause
No power at the sensor
■ Fuse has tripped, not
switched ON, break in
DALI wiring
■ Short circuit
Light level not being
■ Break in wiring
communicated
■ DALI power supply
faulty
Sensor sending motion
■ There is interference,
detection signal when it
e.g. fan, airconditioning
should not
system or other source
of heat, in the detection
zone
■ Animals moving in
detection zone
■ Wind is moving
paper or plants in the
detection zone
■ Sunlight is shining on
the lens
■ Sudden temperature
change due to air
expelled from fans,
open windows, air-
conditioning systems
or other sources of
heat
■ Sensor near Wi-Fi
or other wireless
communication source
Sensor reach change
■ Differing ambient
temperatures
Remedy
■ Activate, change fuse,
turn ON mains switch,
check DALI wiring with
voltage tester
■ Check connections
■ Check cable
■ Adjust detection zone
or fit shrouds, increase
distance
■ Adjust zone or fit
shrouds
■ Change detection zone
■ Mount sensor in a
protected place or
change zone
■ Adjust detection zone
or install in a different
place
■ Install at least 2 m
away from the wireless
communication source
■ Use shrouds to
define detection zone
precisely
- 19 -