Components
Installation
IPE 2700 - 5000 SN 05
The following connectors are used:
PV female cable coupler
PV male cable coupler
DANGER
Extreme danger from electric shock!
x Touching live parts can result in death.
x All electrical work must be carried out by a qualified electrician while observing
the VDE regulations, national and other regulations.
x Multi-Contact MC4 plug connectors are only approved for connection on perma-
nently installed lines.
x Only Multi-Contact crimping pliers may be used to crimp the connectors.
x During preassembly, the connectors must be separated from all other voltage
sources.
x The DC connectors must not be separated under load. The DC circuit must be
interrupted with the DC circuit breaker.
x Provide the lines with corresponding stickers as close as possible to the connec-
tors to prevent confusion.
NOTE
x Any kind of soiling (dust, moisture, etc.) has a negative effect on the connector
system with regard to function over the intended period of use. This particularly
applies to the suitability for use of the seals and the crimping of the contacts.
Therefore, extreme care must be taken to achieve proper processing during as-
sembly.
x Various circular contacts are used with the Multi-Contact MC4 plug connectors
for different conductor cross-sections. The correct tool insert must be used in ac-
cordance with this cross-section. The Multi-Contact MC4 plug connectors can be
equipped with circular contacts for cable cross-section between 4 and 6 mm
x The Multi-Contact crimping pliers and plug connectors can be purchased from
your sales partner.