Tripp-Lite BP192V787C-1PH El Manual Del Propietario página 22

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

6. Diagrams
BUSBAR CONNECTION INSTRUCTIONS
Multi-cabinet systems are provided with paralleling busbars in Cabinet 1. The output from the circuit breaker in
Cabinet 1 is factory wired to the paralleling busbars. Use the included cables to connect the output from the
additional cabinets to the paralleling bars in Cabinet 1. Route the cables from paralleling busbars in Cabinet 1 to
the circuit breaker in the additional cabinets. Cables should be routed through the provided access plates on the
side of the cabinets. Terminate the provided cables to the output terminals of the circuit breaker in each additional
cabinet. Terminate the other end of the cable to the paralleling bus bars located in Cabinet 1.
The system DC output connection to the UPS should be terminated to the paralleling busbars in Cabinet 1.
Notes:
• All internal wiring is UL-listed, MTW, 105C Hi-Flex cable.
• Battery type is CSB HRL FR-series.
• Cabinets with breakers are shipped with the breaker in the off/open position and one of the jumper cables disconnected.
• Terminal block is UL-recognized and rated for 600 VDC.
• Ground connection is (2) #6-250 MCM mechanical lug.
22
Tabla de contenido
loading

Este manual también es adecuado para:

Bp480v200Bp480v300Bp480v400Bp480v500Ebp240v3501

Tabla de contenido