Supplement to section 7.10.4: Update of the IM 153-2Bxx1
Configuration as IM 153-2Bxx1
The firmware update is created separately with each IM 153-2.
The IM 153-2 is integrated in the PCS 7 project.
Procedure
1. Open the SIMATIC Manager.
2. In the component view, select the SIMATC station in which the IM 153-2 is located.
3. Double-click on the "Hardware" object in the detail window.
HW Config opens.
4. Select the IM 153-2 with the firmware you want to update.
5. Select the menu command Target system > Update Firmware.
The "Update Firmware" dialog box opens.
6. Make the settings according to the following table.
7. Click "Run". The firmware is updated.
Setting
Location of the
firmware file
Activate the "new"
firmware
In the redundant system with PROFIBUS DP
Following the firmware update of the active IM 153-2, the subsequent "RESET" automatically switches between the two IM
153-2 modules.
Supplement to section 8.2: Time stamping the input signals with IM 153-2
Rules
You can also use the following digital input module: 6ES7 321-7EH00-0AB0 (1 ms)
Supplement to section 8.4: Redundancy:
Rules for arranging fault-tolerant station components
In a fault-tolerant station, the following conditions must be met for the ET 200M:
Redundantly used modules (DP slave interface modules IM 153-2) must be identical, i.e. they must have the same order
number and the same product version or firmware version.
Interface modules IM 153-4 PN and IM 153-2 HF
A5E02714951-AK, 05/2021
Action
Specify the folder in the "Firmware file" group, in which you have saved the file for updating the
firmware.
Use the "Activate firmware after download" check box to specify the time at which the "new"
firmware should be activated:
Select the "Activate firmware after download" option if the IM 153-2 should automatically
perform a RESET upon successful download of the new firmware. The new firmware in then
active after restart.
Clear the "Activate firmware after download" option if the IM 153-2 no RESET should be
performed upon successful download of the new firmware. The new firmware only takes effect
after the supply voltage is switched off and on again.
15