Phoenix Contact MCR-F-UI-DC Manual De Instrucciones página 27

Ocultar thumbs Ver también para MCR-F-UI-DC:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 40
8. Technical data
Current/voltage input
Input signal
Cut-off frequency
Ascent time (10-90 %)
Output
Output signal
Max. output signal
Load
Alignment zero point / end value
Switching output
General data
Supply voltage
Current consumption (without load)
Transmission error
Temperature coefficient
Test voltage:
Protection circuit
Ambient temperature range
Operation indicator
Control panel
Installation position/assembly
Dimensions
Type of connection
Conductor cross section
Type of housing
Conformity / Approvals
Conformance
Immunity to interference
Noise emission
Approval
current/voltage
current/voltage
input/power supply
input/output
output/power supply
(W / H / D) in mm
with EMC directive
according to
according to
U
PROCESS CONTROL EQUIPMENT
FOR HAZARDOUS LOCATIONS
LISTED
31ZN
Class I Div 2 Groups A, B, C, D
A) This equipment is suitable for use in Class I, Division 2, Groups A, B, C
and D or non-hazardous locations only.
B) WARNING - explosion hazard - substitution of components may
impair suitability for Class 1, Division 2.
C) WARNING - explosion hazard - do not disconnect equipment unless
power has been switched off or the area is known to be non-hazardous.
MCR-F-UI-DC
0...10 V / 0...20 mA
10 Hz
25 ms
0...10 V / 10...0 V, 0...5 V / 5...0 V oder
0(4)...20 mA / 20...0(4) mA
25 mA / 12.5 V
≤ 500 Ω / ≥ 500 Ω
± 25 % / ± 25 %
PNP transistor output, switches the
supply voltage to terminal SW, can carry
a load of 100 mA, not short-circuit proof
20 ... 30 V DC
< 60 mA (without switching output)
< 0.15 % of end value (typ. 0.1 %)
< 0.015 %/K (typ. 0.01%/K)
1.5 kV, 50 Hz, 1 min.
1.5 kV, 50 Hz, 1 min.
1.5 kV, 50 Hz, 1 min.
transient protection, polarity protection
-20 °C to +65 °C
LC display
membrane keypad with 3 keys and LCD
any, preferably horizontal
45 / 75 / 110
pluggable screw connection
2
0.2 – 2.5 mm
(AWG 24-14)
ASA-PC (V0)
c
2004/108/EC
EN 61000-6-2
EN 61000-6-4
2814605