PFP 700
CAUTION
Please observe the following to ensure that the PFP
is not damaged during operation:
– Check the mains voltage setting of the replaced
unit – see setting of switch S1 (115 V or 230 V).
– If necessary, adjust the setting of switch S1 on
the new unit.
PFR 704
CAUTION
Please observe the following to ensure that the
PFR is not damaged during operation:
– The relay inputs must only be connected to the
permitted voltages (see connection diagram B
for PFR 704).
Wiring
WARNING
Electric shocks can be fatal! Before working on
possible live components ensure the unit is discon-
nected from the power supply.
Disconnect the system from the electrical power
supply.
▷
Connection only with permanent wiring. Different
phases of a three-phase current system must not
be installed at the inputs.
Wire as shown on the connection diagram.
Connection diagrams
A = PFP 700
B = PFR 704
A
PFP 700
S0
O
F1
30a
L1
I
32c
N
U
S1
S1
230 V
115 V
8ace
24 V=
600 mA
12ace
0 V
I
B
PFR 704
230 V~
2e
2a
115 V~
24 V=/~
2c
1
0 V
4e
10e
230 V~
10a
115 V~
10c
24 V=/~
2
0 V
12e
18e
230 V~
115 V~
18a
18c
24 V=/~
3
20e
0 V
26e
230 V~
26a
115 V~
26c
24 V=/~
4
0 V
28e
Commissioning
CAUTION
Mains voltage may only be connected by trained
personnel.
Check the electrical wiring, switch settings and
parameter settings of the 19" boards and the
burner settings before commissioning.
Switch on the system.
PFP 700
Apply voltage to terminal 30a.
4 Switch on power supply PFP 700.
▷
The green LED will light up.
PFR 704
▷
The green LED will light up if a relay is activated.
7
6a
6e
8a
8e
8c
6c
16a
16e
14a
14e
14c
16c
24a
24e
22a
22e
22c
24c
32a
32e
30a
30e
30c
32c