CHECKING GAS CONNECTIONS
WARNING
WARNING
Pressure Testing Gas Supply Piping System
Test Pressures in Excess Of 1/2 PSIG (3.5 kPa):
1. Disconnect the appliance, including the main gas valve (control valve) and equipment shutoff valve,
from the gas supply piping system. Pressures greater than 1/2 PSIG will damage the regulator.
2. Cap off the open end of the gas pipe where the equipment shutoff valve was connected.
3. Open the gas supply tank valve or use compressed air to pressurize the supply piping system.
4. Check all joints of the gas supply piping system. Use a mixture of liquid soap and water in the gas joints
to check for leaks—bubbles may indicate a leak.
5. Immediately correct all leaks.
6. Reconnect the appliance and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa):
1. Close equipment shutoff valve (see Fig. 8).
2. Open the gas supply tank valve or use compressed air to pressurize the supply piping system.
3. Check all joints from the gas meter to equipment shutoff valve (see Fig. 9.1 & 9.2).
4. Use a mixture of liquid soap and water in the gas joints to check for leaks—bubbles may indicate a leak.
5. Immediately correct all leaks.
Pressure Testing Appliance Gas Connections:
1. Open the equipment shutoff valve (see Fig. 8).
2. Open the gas supply tank valve.
3. Ensure the control knob of the appliance is in the OFF position.
4. Check all joints from the equipment shutoff valve to the control valve
(see Fig. 9.1 & 9.2). Use a mixture of liquid soap and water in the gas
joints to check for leaks—bubbles may indicate a leak.
5. Light the appliance (see OPERATION, page 13). Check all other internal
joints for leaks.
6. Turn off the appliance (see TO TURN OFF GAS TO THE APPLIANCE, page 13).
Fig. 9.1—Checking Gas Joints (Propane/LP Only)
Gas Control Valve
©2017 Pinnacle Climate Technologies
Installation (cont.)
After installing or servicing the appliance, test all gas piping and connections for leaks.
Immediately correct all leaks.
Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to
all joints. There may be a leak if bubbles form. Immediately correct all leaks.
Equipment
Shutoff
Valve Propane/
LP Supply
Tank
Fig. 9.2—Checking Gas Joints (Natural Gas Only)
Gas Control Valve
10
Vented Gas Log Appliance User's Manual