Make sure air actuator tubing is
securely attached to the pump.
Bond in accordance with applicable codes.
NOTE: Pump model illustrated may differ from your
actual product.
13. Make Electrical Connections - Dedicated Circuit Models
WARNING: Risk of electrical shock. To reduce the risk of electrical shock, connect the pump to a
properly grounded Ground-Fault Circuit-Interrupter (GFCI). This will provide additional protection
against line-to-ground shock hazard. A 120 V, 15 A dedicated circuit is required.
WARNING: Risk of electrical shock. Make sure the power has been disconnected before
performing the following procedures.
NOTE: Heater is optional. Some models will not have the heater.
Locate and secure the supplied junction box a minimum of 1-1/2" (3.8 cm) above the subfloor.
The whirlpool controls and system have been prewired at the factory. A qualified electrician should
make a routine service connection to the junction box.
Connect service to the junction box. The 60 Hz model junction box contains black and white wires
and a ground lug.
A 120 V, 15 A dedicated circuit is required. Provide a Class A Ground-Fault Circuit-Interrupter
(GFCI).
Provide a separate equipment grounding conductor for the inside ground or ground lug. The
conductor must not be connected to any current-carrying conductor.
Bond in accordance with national and local codes.
Repeat the procedures for heater. All wiring of the heater has been completed at the factory.
1105582-2-B
Pump
Electrical
Cord
18
Junction box should be
wired as shown.
Ground
Neutral
(White)
Electrician to
provide suitable
Neutral
strain relief.
Wire Connectors
From Pump
Line
(Black)
Line
Sterling