NCV Mode
Receiver:
NCV Mode
The NCV (Non-Contact Voltage) mode is used to
verify that a wire is Energized. This method does
not require the use of the Transmitter. The Receiver
will detect an Energized cable if the voltage is
between 90 V and 600 V AC and between 40 Hz
and 400 Hz. No current flow is necessary.
1. Turn on the Receiver and press the NCV button.
2. Hold the Receiver with the Tip Sensor facing the
target area.
3. Scan the target area with the Tip Sensor to find the
highest signal level, then begin tracing the detected
wire. For precise pinpointing of hot wire versus
neutral wire, increase or decrease sensitivity by
pressing + or – on the keypad.
4. Press ENTER when complete to return to the
home screen.
Note:
For safety, before working with wires, always verify
that they are De-energized with an additional tester.