fixed wiring, unless a switch complying with a
contact separation in all poles of at least 3 mm.
9. If the supply cord is damaged, it must be
replaced by the manufacturer, its service agent
or similarly qualified persons in order to avoid a
hazard.
WARNING: This heater is not equipped with
a device to control the room temperature.
Do not use this heater in small rooms when
they are occupied by persons not capable
of leaving the room on their own, unless
constant supervision is provided.
2. Mounting
2.1 Integrated in ceiling, put in exposed grid
(See fig A and B)
1. Place the cassette in the required ceiling
square. Minimum design height "H" for
dismounting, T-profile 32x15: 150 mm, T-profile
38x24: 200 mm. NOTE! Avoid fixing vertical bars
in the T-profile where a heating panel is to be
installed. The panel fills out the whole square.
2. Connect the panel.
Minimum distance
Fig A
A: Ceiling 80mm
C: Obstacle 500mm
Minimum mounting distance
B: Wall
50mm
D: Floor
Mounting
Fig. 1
Bracket mounting
Fig C
Fig. 1: Minimum mounting distance
A
False ceiling
1800mm
Min 1,5 mm²
Max 2100 W
MAGNUM Sol
3. The last page in this mounting instruction
is to be filled out and fixed adjacent to the
distribution board and it has to contain
(drawing) the locations of the heating units.
2.2 Bracket mounting (See fig A and C)
1. When mounting in gypsum board, make sure
that the panel frame is anchored in the beam
behind. During long-term high temperatures
the strength of the board is reduced.
2. Measure, drill and screw the panel frame to
the ceiling.
3. Hook the panel brackets to the panel frame
on the ceiling
4. Connect the panel.
3. Scedule or pictures of the installation
The Middle page in this mounting instruction
is to be filled out and fixed adjacent to the
distribution board and it has to contain (pictures
or drawing) the locations of the heating units
distribution board and it has to contain (pictures
or drawing) the locations of the heating units.
Mounting
Integrated in ceiling
Fig B
Ceiling
Wall, long side of the unit
Wall, short side of the unit
Obstacle
Floor
Fig. 1
Fig. 2
A
C
B
Min 1,5 mm²
Max 2100 W
Min.distance
[mm]
80
50
50
500
1800
Fig. 2
C
D
7