Sensor Connection - Nibe HPAC 28 Instrucciones De Instalación Y Mantenimiento

Ocultar thumbs Ver también para HPAC 28:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

The existing flow line sensor (FG) should be replaced
with the one that is mounted in the HPAC.
Cut off the existing cables as close to the edge board
connector as possible on terminal X4 positions 15 –
16 on the EBV card (2). Ensure that the cut cables do
not touch each other or any metal. Connect the
enclosed extension cable from the flow line sensor in
the HPAC straight to the screw terminal in the same
position on the EBV card.
FG
If the room sensor (RG 10) is to be used, this is con-
nected to the EBV-card (2) at terminal X1 positions 3,
4 and 14.
FIGHTER 1120
2
FIGHTER 1220
2
Electrical connections

Sensor connection

I II III
A B
I II
I II
5 0 . 0
C
V a r m v a t t e n t e m p . 1 .0
HPAC 28
RG 10 (accessory)
RG 10 (tillbehör)
6 1 2
X1
X4
GB
27
Flow sensor
Framledningsgivare
Tabla de contenido
loading

Tabla de contenido