Product Description - INIM Electronics enea EM411R Manual De Instrucciones

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

The EM411R module allows you to interface a conventional line (up to 32 conventional detectors or call points) to
an INIM analog-addressable control panel
On the back of the module you will find a label showing the technical specifications and the distinctive serial
number which identifies the device.
F
EM411R
CONVENTIONAL ZONE MODULE
G
*00000009*
EM411R 00000009 EM411R 00000009
A
Conventional zone LED
B
Short circuit isolator LED
C
D
E
Removable anchor locations
F
Technical specifications/serial-number sticker
G
Removable serial-number stickers
Terminals
Terminals for the input
1
Loop IN +
connection with the
2
Loop IN -
3 Loop OUT +
Terminals for the output
connection with the
4
Loop OUT -
Conven-
5
tional zone
Conventional line con-
+
Conven-
6
tional zone -
7
8
C1
Common switch 1
9
NC1
Normally closed switch 1
10
NO1
Normally open switch 1
11
C2
Common switch 2
12
NC2
Normally closed switch 2
13
NO2
Normally open switch 2
LED
Colour
Red
A
Yellow
B
Yellow
Green - ON solid
C
Green blinking
EM411R
Conventional zone module

Product description

MADE
IN
ITALY
G
2011/03
FW.01.01
Output LED
Terminals
Description
It is not necessary to respect
the input/output configura-
tion of the terminals as the
loop.
Loop IN and OUT terminals
However, for wiring congru-
ence, it is advisable to follow
loop.
the order indicated in this
The line must be terminated
with 22μF capacitor as
nection
shown in wiring diagram
Not used
The two outputs activate
simultaneously and cannot
be activated separately.
Alarm on conventional line
Fault (open or short) on conventional line
Short circuit on loop cable
Output relay active
Module is communicating
E
Note
are interchangeable.
table.
Function
A
B
TECHNICAL
SPECIFICATIONS
Power supply
Current draw in standby
status
Maximum current draw in
alarm status
Conventional zone End Of
Line
Open fault threshold with no
load
Open fault threshold with
load
Alarm threshold
Short fault threshold
Relay contact rating
Operating temperature
Humidity
(without condensation)
Height
Width (with anchor loca-
tions)
Width
(without anchor locations)
Depth
(with terminal boards)
Depth
(without terminal boards)
Weight
C
E
D
EM411R
19-30Vdc
1.2 mA
60 mA
22μF 35v
capacitor
220 nF
2.2 μF
12 mA
50 Ohm
1 A / 30
Vdc
-5°C/
+40°C
95% RH
53 mm
100 mm
78 mm
29 mm
19 mm
66 g
3