Operation (see drawing 3)
4
3a. Static condition, no consumption
Both check valves are closed. The pressure in the intermediary chamber remains 50 kPa lower
than the inlet pressure, keeping the relief valve closed.
3b. Pressure, flow
The first and second check valves are open. The water circuit pressure upstream of the relief
valve keeps it closed. The pressure in the intermediate chamber is at least 50 kPa lower than the
inlet pressure.
3c. Back siphoning, discharge intermediate zone
When the water circuit pressure drops off, both check valves are closed. The relief valve is opened
and the water from the intermediary chamber is drained through the water outlet. This creates an
atmospheric "break" between the water circuit and the polluted or unknown quality water on the
outlet site of the device.
3d. Back pressure
• Second check valve is leak-tight: no discharge.
• Second check valve fouled: the relief valve will open and drain a quantity of water, so that the
pressure in the intermediary chamber remains lower than the water circuit pressure.
Approvals
Kiwa / WRAS / NF / DVGW
SITAC / Belgaqua / SVGW / UNI / SINTEF / ETA
For more information about the BA BM device, see our website www.waterprotection.com.
The photos and description contained in this brochure are solely intended as an indication, Watts Industries reserves the right to
make technical and design changes to its products without prior notice.
Tabla de contenido
loading

Este manual también es adecuado para:

Ba bm 015Ba bm 020Ba bm 025Ba bm 032Ba bm 040Ba bm 050

Tabla de contenido