Faults and Alarms
Number / Fault
Cause
F074
4 mA at analog input 2, slave 1 fallen short of
AnInp2 SL1
not Compact PLUS
F075
4 mA at analog input 3, slave 1 fallen short of
AnInp3 SL1
not Compact PLUS
F076
4 mA at analog input 1, slave 2 fallen short of
AnInp1 SL2
not Compact PLUS
F077
4 mA at analog input 2, slave 2 fallen short of
AnInp2 SL2
not Compact PLUS
F078
4 mA at analog input 3, slave 2 fallen short of
AnInp3 SL2
not Compact PLUS
F079
No telegram has been received by the SCB
(USS, peer-to-peer, SCI) within the telegram
SCB telegram failure
failure time.
not Compact PLUS
F080
Fault during initialization of the board at the
DPR interface
TB/CB initialization
fault
F081
Heartbeat-counter of the optional board is no
longer being processed
OptBrdHeartbeat-
Counter
F082
No new process data have been received by
the TB or the CB within the telegram failure
TB/CB telegram failure
time.
12-8
Counter-measure
Check the connection of the signal source to
the SCI1 (slave 1) -X428: 7, 8.
Check the connection of the signal source to
the SCI1 (slave 1) -X428: 10, 11.
Check the connection of the signal source to
the SCI1 (slave 2) -X428: 4, 5.
Check the connection of the signal source to
the SCI1 (slave 2) -X428: 7, 8.
Check the connection of the signal source to
the SCI1 (slave 2) -X428: 10, 11.
- Check the connections of the SCB1(2).
- Check P704.03"SCom/SCB Tlg OFF"
- Replce SCB1(2)
- Replace CU (-A10)
Fault value r949:
1: Board code incorrect
2: TB/CB board not compatible
3: CB board not compatible
5: Error in configuration data
6: Initialization timeout
7: TB/CB board double
10: Channel error
Check the T300/CB board for correct
contacting, check the PSU power supply,
check the CU / CB / T boards and check the
CB initialization parameters:
- P918.01 CB Bus Address,
- P711.01 to P721.01 CB parameters 1 to 11
Fault value r949:
0: TB/CB heatbeat-counter
1: SCB heartbeat-counter
2: Additional CB heartbeat-counter
- Acknowledge the fault (whereby automatic
reset is carried out)
- If the fault re-occurs, replace the board
concerned (see fault value)
- Replace ADB
- Check the connection between the subrack
and the optional boards (LBA) and replace, if
necessary
Fault value r949:
1 = TB/CB
2 = additional CB
- Check the connection to TB/CB
- Check P722 (CB/TB TlgOFF)
- Replace CB or TB
6SE7087-8JP50
Operating Instructions
SIMOVERT MASTERDRIVES
08.2006