6
ADJUST SUPPLY STOP; Fig. 13
IMPORTANT: To avoid overflowing, the SUPPLY STOP (3)
must never be opened to the point where the flow from
the valve exceeds the flow capacity of the fixture. Valve
is designed to provide stated flush volume with a 25 gpm
flow rate for toilet and 10 gpm flow rate for urinal.
1. Remove COVER (2) from SUPPLY STOP (3).Turn on water
supply 1/4 turn to 1/2 turn(CCW) and test for leaks.
Note: Unit may flush for approximately 5 to 10 sec. when
water is first turned on.
2. Push down on HANDLE (4) to initiate flush.
3. Adjust SUPPLY STOP (3) after each flush until the stated
flush volume is achieved, no splashing occurs and the fixture
is properly cleansed.
4. When adjustment is complete, reinstall COVER (2) and
tighten to ensure vandal-resistance.
7
HOW TO RETROFIT OUR VALVE; Fig. 14
Replaces Industry Standard Manual and Electronic Valves)
Note: In most Retrofits the wall escutcheon, supply
stop, cover tube and vacuum breaker do not have to be
replaced. If these items do need replacement they must
be purchased separately or order the complete flush valve
assembly from American Standard.
1. Remove COVER (1) from SUPPLY STOP (2) if installed.
Fig. 14.
2. Turn water supply off. Fig. 14.
3. Unthread COUPLING NUT (3) and VACUUM BREAKER
COUPLING NUT (4). Remove FLUSH VALVE (5). Fig. 4a.
4. Clean all threaded connections before installing the new
flush valve. Fig. 14a.
5. Refer to Sections 4, 5 and 6 to complete the retrofit installation.
Fig. 14b.
8
LEFT OR RIGHT HAND INSTALLATION;
Fig. 15
1. The FLUSH VALVE can be installed either as a right or left
hand installation.
2. Orientate the FLUSH VALVE as shown in Fig. 13 to desired
position for a left or right hand installation.
Fig. 13
Fig. 14
Fig. 14a
5
2
CLEAN
1
CONNECTIONS
3
4
Fig. 15
Right or Left Hand Installation
Left Hand
6
REMOVE COVER
3
2
COUNTER-CLOCKWISE
OPENS CONTROL STOP
CLOCKWISE CLOSES
CONTROL STOP
Fig. 14b
Right Hand
M965874 Rev. 1.1 (1/19)