Installation, Setup and Operation Guide
I. SAFETY NOTICES
ATTENTION
- WARNING: NEVER touch any of the electrical components directly when equipment is
removed from package.
- The EBC1 Expansion board can not be used simultaneously with other expansion
boards (EBA, EBB or EBC1).
II. GENERAL INFORMATION
This guide provides information for the correct installation, configuration and
operation of EBC.01, EBC.02 and EBC.03 Boards for CFW-09. These boards are
applied on reading the encoder signals. All board functions are described on table 1.
Table 1: Models of EBC1 boards and their respective functions.
Encoder signals Input
Isolated internal power supply for encoder (12 V)
Isolated internal power supply for encoder (5 V)
III. PACKAGE CONTENT
- 1 Expansion Board packaged in anti-static plastic sheets.
NOTE
- Check if the model indicated on the package label matches the ordered ones.
- Remove the Expansion board from the anti-static plastic package carefully.
- Hold the board only on the sides. Do not touch directly on the components.
1. EBC1 BOARD INSTALLATION
The EBC1 board is installed on the CC9 control board, secured by spacers. For
installing the board, follow the guidelines bellow:
Step 1 With the frequency inverter not energized, remove the CFW-09 frontal cover;
Step 2 If the inverter is Size 1 , remove also the lateral cover;
Step 3 Set the board configuration according to table 2;
Step 4 Carefully insert terminal block XC3 (EBA/EBB board) into the female connector
XC3 on the CC9 control board;
Step 5 Check if all pins of the XC3 connector are connected correctly;
Step 6 Press on the EBC1 board center (near XC3) and on the left top edge until complete
insertion of the connector and plastic spacer;
Step 7 Secure the board to the 2 metallic spacers with the 2 screws provided.
EBC1 EXPANSION BOARD
FUNCTIONS
EBC1 Model
01
02
03
1