GAS BURNERS AND RELEVANT GAS TRAINS APPROVED ACCORDING TO EN 676
Gas train L
Ø
C.T.
Code
1"
-
3970145
1/2
1"
-
3970180
1/2
2"
-
3970146
2"
3970160
2"
-
3970181
2"
3970182
DN 65
-
3970147
DN 65
3970161
DN 80
3970148
DN 80
3970162
(C)
GAS TRAIN COMPONENTS
Code
Filter
5
3970145
GF 515/1
3970180
3970146
GF 520/1
3970160
3970181
3970182
3970147
GF 40065/3
3970161
3970148
GF 40080/3
3970162
Burner
RS 70
RS 100
RS 130
-
-
-
-
Components
Pressure governor
6
FRS 515
Multiblock MB DLE 415
FRS 520
Multiblock MB DLE 420
FRS 5065
FRS 5080
D722
D953
13
14
Code
Code
3010123
3000843
3010123
3000843
3010123
-
-
-
3010123
-
-
-
3010123
3000825
-
3000825
3010123
3000826
-
3000826
Solenoids
8 - 9
DMV-DLE 512/11
DMV-DLE 520/11
DMV-DLE 5065/11
DMV-DLE 5080/11
8

GAS LINE

• The gas train must be connected to the gas
attachment 1)(A), using flange 2), gasket 3)
and screws 4) supplied with the burner.
• The gas train can enter the burner from the
right or left side, depending on which is the
most convenient, see fig.(A).
• Gas solenoids 8)-9)(B) must be as close as
possible to the burner to ensure gas reaches
the combustion head within the safety time
range of 3 s.
• Make sure that the pressure governor calibra-
tion range (colour of the spring) comprises the
pressure required by the burner.
GAS TRAIN (B)
It is type-approved according to EN 676 Stand-
ards and is supplied separately from the burner
with the code indicated in Table (C).
KEY (B)
1 - Gas input pipe
2 - Manual valve
3 - Vibration damping joint
4 - Pressure gauge with pushbutton cock
5 - Filter
6 - Pressure governor
7 - Minimum gas pressure switch
8 - Safety solenoid
9 - Adjustment solenoid
Two adjustments:
• ignition delivery
• maximum delivery
10 - Standard issue burner gasket with flange
11 - Gas adjustment butterfly valve
12 - Burner
13 - Gas valve 8)-9) leak detection control
device.
In accordance with EN 676 Standards, gas
valve leak detection control devices are
compulsory for burners with maximum out-
puts of more than 1200 kW; therefore only
for model RS 130.
14 - Gas train/burner adaptor.
P1 - Pressure at combustion head
P2 - Pressure down-line from the pressure gov-
ernor
P3 - Pressure up-line from the filter
L - Gas train supplied separately with the code
indicated in Table (C)
L1 - The responsibility of the installer
KEY TO TABLE (C)
C.T.=Gas valves 8) - 9) leak detection control
devices:
- = Gas train without gas valve leak detec-
tion control device; device that can be
ordered separately and assembled sub-
sequently (see Column 13).
= Gas train with assembled VPS valve
leak detection control device.
13 = VPS valve leak detection control device.
Supplied separately from gas train on
request.
14 = Gas train/burner adaptor.
Supplied separately from gas train on
request.
Note
See the accompanying instructions for the
adjustment of the gas train.