Fuel Consumption; Natural Gas - Briggs & Stratton FORTRESS Manual De Instalación Y Operación

Generador de reserva monofásico enfriado por aire
Ocultar thumbs Ver también para FORTRESS:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Fuel Consumption

Estimated fuel supply requirements at half and full load for
natural gas and LP vapor fuels are shown here.
LP Vapor (Propane)
Cu Ft/Hr
Full
Gal/Hr
Load
(liquid)
BTU/Hr
Cu Ft/Hr
Gal/Hr
1/2 Load
(liquid)
BTU/Hr
Cu Ft/Hr
Gal/Hr
Exercise
(liquid)
BTU/Hr

Natural Gas

Cu Ft/ Hr
Full Load
BTU / Hr
Cu Ft/ Hr
1/2 Load
BTU / Hr
Cu Ft/ Hr
Exercise
BTU / Hr
22
10 kW
65.6
1.82
164000
42.8
1.18
107000
23.6
0.65
59000
10 kW
169
169000
111
111000
60
60000
Recommended
Energy Content of
Fuel:
Heating Value:
BTU per gallon liquid
(gross*)
BTU per Cubic feet
(vapor)
Natural Gas
Propane
(LP Vapor)