3. Specifications
Model
Sound level
Refrigerant
Net weight
R410A
MPa
Design pressure
R134a
MPa
Water
MPa
Connectable
Total capacity
Outdoor unit
Model/Quantity
Temp. range of
Outdoor temp.
Heating
Inlet Water temp.
Temp. range of
Outdoor temp.
Cooling
Inlet Water temp.
4. Confirmation of parts attached
1 Strainer
2 Heat insulation material
5. Lifting method
Caution:
Be very careful when carrying the product.
- Do not have only one person to carry product if it is more than 20 kg.
- PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
6. Installation of unit and service space
6.1. Installation
•
Using the anchoring holes shown below, firmly bolt the unit to the base.
[Fig. 6.1.1] (P.2)
A 4-ø14 (Anchoring hole) B (Top view)
Bases
•
Be sure to install unit in a place strong enough to withstand its weight. If the
base is unstable, reinforce with a concrete base.
•
The unit must be anchored on a level surface. Use a level to check after
installation.
•
If the unit is installed near a room where noise is a problem, using an anti-
vibration stand on the base of the unit is recommended.
7. Water pipe installation
•
Light pipes are similar to other air-conditioning pipes, however, please ob-
serve the following precautions during installation.
•
Before a long period of non use, purge the water out of the pipes and thor-
oughly let them dry.
•
Use a closed water circuit.
•
When using the unit for cooling, add brine to the circulating water to prevent it
from freezing.
•
When installed in a low-ambient temperature environment, keep the water cir-
culating at all times. If that is not possible, purge the water out of the pipes
completely.
PWFY-P100VM-E-BU
44dB<A>
R134a
1.1 kg
60 kg
4.15
3.60
1.00
PURY-P * Y(S)HM-A (-BS)
-20~32 ˚CWB (59~90 °F)
10~70 ˚C (50~158 °F)
_
_
3 Connecter sets
2
4 Expansion joint
PWFY-P100VM-E-AU
29dB<A>
-
35 kg
4.15
-
1.00
50~100 % of outdoor unit capacity
-20~32 ˚CWB (-4~90 °F) PURY - series
-20~15.5 ˚CWB (-4~60 °F) PUHY - series
-5~43 ˚CDB (23~110 °F) PURY - series
-5~43 ˚CDB (23~110 °F) PUHY - series
2 (PWFY-P200VM-E-AU)
Warning:
•
Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal
injury.
•
Have installation work in order to protect against earthquake.
Any installation deficiency may cause unit to fall down, resulting in a
personal injury.
6.2. Service space
•
Please allow for the following service spaces after installation.
(All servicing can be performed from the front of the unit)
[Fig. 6.2.1] (P.2)
Model
a
PWFY-P100VM-E-BU
400
PWFY-P100VM-E-AU
400
PWFY-P200VM-E-AU
400
A Piping space (right side)
C Service space (front side)
•
Do not use the water used for this unit for drinking or food manufacturing.
•
Do not use steel pipes as water pipes.
•
When the ambient temperature is 0 ˚C or lower during stop operation, keep the
water circulating at all times, or purge the water out of the pipes completely.
Model
Water inlet
PWFY-P100VM-E-BU
PT 3/4 Screw
PWFY-P100VM-E-AU
PT 3/4 Screw
PWFY-P200VM-E-AU
*1 When the attached
PT 1 Screw*1
expansion joints are
installed.
PWFY-P200VM-E-AU
29dB<A>
-
38 kg
4.15
-
1.00
PURY-P * Y(S)HM-A (-BS)
PUHY-P * Y(S)HM-A (-BS)
10~40 ˚C (50~104 °F)
10~35 ˚C (50~95 °F)
b
c
300
600
300
600
300
600
B Top view
Water outlet
PT 3/4 Screw
PT 3/4 Screw
PT 1 Screw*1
7