WEG CFW100 Referencia Rápida página 16

Convertidor de frecuencia
Ocultar thumbs Ver también para CFW100:
Idiomas disponibles

Idiomas disponibles

CALL NOW 800-985-6929
Quick Reference of Parameters, Alarms and Faults
Param.
P375
Temperature NTC
(*)
P397
Regener. Slip Compens.
P399
Motor Rated Efficiency
P400
Motor Rated Voltage
P401
Motor Rated Current
P402
Motor Rated Speed
P403
Motor Rated Frequency
P404
Motor Rated Power
P407
Motor Rated Power Factor
P409
Stator Resistance
P680
Logical Status
P681
Speed in 13 bits
P682
Serial/USB Control
P683
Serial/USB Speed Ref.
P684
CO/DN Control
(**)
P685
CO/DN Speed Ref.
(**)
16 | CFW100
CALL NOW 800-985-6929
http://www.automatedpt.com
Description
0 to 100 ºC
0 = Inactive
1 = Active
50.0 to 99.9 %
0 to 240 V
0.0 to 10.0 A
0 to 9999 rpm
0 to 300 Hz
0 = 0.16 HP (0.12 kW)
1 = 0.25 HP (0.19 kW)
2 = 0.33 HP (0.25 kW)
3 = 0.50 HP (0.37 kW)
4 = 0.75 HP (0.55 kW)
5 = 1.00 HP (0.75 kW)
0.50 to 0.99
0.01 to 99.99
Bit 0 to 4 = Reserved
Bit 5 = 2
Bit 6 = Config. status
Bit 7 = Alarm
Bit 8 = Running
Bit 9 = Enabled
Bit 10 = Forward
Bit 11 = JOG
Bit 12 = Remote
Bit 13 = Undervoltage
Bit 14 = Reserved
Bit 15 = Fault
-32768 to 32767
Bit 0 = Ramp Enable
Bit 1 = General Enable
Bit 2 = Run Forward
Bit 3 = JOG Enable
Bit 4 = Remote
Bit 5 = 2
Bit 6 = Reserved
Bit 7 = Fault Reset
Bit 8 to 15 = Reserved
-32768 to 32767
See options in P682
-32768 to 32767
http://www.automatedpt.com
Adjustable Range
Ramp
nd
Ramp
nd
Factory Setting
Prop.
ro
1
cfg
67.0 %
cfg, V V W
220 (230)
cfg, V V W
1.4 A
cfg
1720 (1310) rpm
cfg
60 (50) Hz
cfg
2
cfg, V V W
0.69
cfg, V V W
10.63
cfg, V V W
ro
ro
ro
ro
ro
ro