Wiring Diagram - Eaton CROUSE-HINDS Champ PFMA Serie Información De Instalación Y Mantenimiento

Reflector led
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

WIRING DIAGRAM

3L - 7L WIRING UNV1
HEATSINK
GREEN/YELLOW
DRIVER HOUSING
DRIVER
(YELLOW/BLACK)
LINE
NEUTRAL
POSITIVE
LED PCB 1
NEGATIVE
GROUND
Figure 4
3.
Re-install back cover/heat sink and tighten all nine (9) mounting screws to 22 in.-
lbs. (2.5 N-m). Be sure wires are not pinched during cover installation.
Replace any damaged or missing cover screws. Use only stainless steel
#10-24 x 0.75"cover screws.
4.
To make final vertical adjustment, loosen the pivot bolts on the floodlight yoke to
position floodlight at the desired angle.
5.
Rotate the floodlight housing to the desired position.
6.
Tighten the two (2) pivot bolts to 45 ft.-lbs. (61 N-m).
7.
Turn power on.
To avoid overheating of the floodlight:
Do not position the floodlight beyond the aiming range limits.
IF 1891 • 08/19
SUPPLY WIRE
G
N
L
3X
3 POLE SPLICE
CONNECTOR
BLACK
WHITE
(DC-)
(DC+)
G
N
L
G
N
L
(GREEN)
(WHITE)
(BLACK)
INPUT
BLACK/WHITE
PURPLE (+)
GRAY (-)
OUTPUT
DIMMING LEADS
+ (RED)
0-10 VDC SIGNAL
- (BLUE)
10V = 100% LIGHT OUTPUT
2X
2 POLE SPLICE
CONNECTOR
(YELLOW/RED)
S1 -
S2 +
WARNING
Copyright
HEATSINK
3X
DRIVER HOUSING
2 POLE SPLICE
CONNECTOR
Leads not used
LINE
NEUTRAL
POSITIVE
NEGATIVE
GROUND
Figure 3
MAINTENANCE
Perform visual, electrical and mechanical inspections on a regular basis. The
environment and frequency of use should determine this. However, it is
recommended that checks be made at least once a year. We recommend an
Electrical Preventive Maintenance Program as described in the National Fire
Protection Association Bulletin NFPA 70B: Recommended Practice for Electrical
Equipment Maintenance (www.nfpa.org).
The lens should be cleaned periodically to ensure continued lighting performance.
To clean, wipe the lens with a clean, damp cloth. If this is not sufficient, use a
mild soap or a liquid cleaner such as Collinite NCF or Duco #7. Do not use an
abrasive, strong alkaline or acid cleaner. Damage may result.
Visually check for undue heating evidenced by discoloration of wires or other
components, damaged parts or leakage evidenced by water or corrosion in the
interior. Replace all worn, damaged or malfunctioning components and clean
gasket seals before putting the luminaire back into service.
Electrically check to make sure that all connections are clean and tight.
Mechanically check that all parts are properly assembled.
If the lens cover is removed from the fixture, the bezel gasket must be replaced
to maintain restricted breathing ratings.
REPLACEMENT PARTS
Crouse-Hinds Champ
performance. However, should the need for replacement parts arise, they are available
through your authorized Crouse-Hinds distributor. Assistance may also be obtained
through your local Crouse-Hinds representative or the Crouse-Hinds Sales Service
Department, 1201 Wolf Street, Syracuse, New York 13208, Phone 866-764-5454.
2019, Eaton's Crouse-Hinds Division
®
9L - 15L WIRING UNV1
SUPPLY WIRE
G
N
BLACK
WHITE
(DC-)
GREEN/YELLOW
(DC+)
G
N
G
N
(GREEN)
(WHITE)
INPUT
DRIVER
OUTPUT
+ (RED)
- (BLUE)
(YELLOW/BLACK)
(YELLOW/RED)
LED PCB 1
S1 -
S2 -
S2 +
(JUMPER WIRE - BLACK)
S1 +
LED Floodlights are designed to provide years of reliable lighting
®
L
3X
3 POLE SPLICE
CONNECTOR
L
3X
2 POLE SPLICE
L
CONNECTOR
(BLACK)
BLACK/WHITE
PURPLE (+)
GRAY (-)
DIMMING LEADS
0-10 VDC SIGNAL
Leads not used
10V = 100% LIGHT OUTPUT
2X
2 POLE SPLICE
CONNECTOR
Page 2
Tabla de contenido
loading

Este manual también es adecuado para:

Champ crouse-hinds serieChamp pfma serie

Tabla de contenido