Standard Versions Technical Data (°) - AERMEC VENICE Manual Del Usuario

Enfriador agua / agua, bombas de calor
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

5.2
STANDARD VERSIONS TECHNICAL DATA (°)
Cooling capacity
Total absorbed power
Evaporator water flow rate
Condenser water flow rate
Condenser pressure drop
Condenser water consumption at 16 °C (1)
Condenser water pressure drop at 16 °C
ENERGY INDEXES
EER
ESEER
ELECTRICAL DATA
Power supply
Absorbed current
Maximum current
Peak current
COMPRESSORS (SCROLL)
Number per circuit/type
EVAPORATOR (PLATES)
Number
Hydraulic connections
CONDENSER (PLATES)
Number
Hydraulic connections
STORAGE
Water storage
PUMP
Absorbed power
Absorbed current
Effective pressure to the plant
SOUND DATA
Sound power level
Sound pressure
DIMENSIONS
Height
Width
Depth
EMPTY weight
In cooling mode
- Outlet water temperature
- Water inlet temperature to condenser 30 °C
- ∆t
- Sound pressure measured in 85 m 3 semi-
kW
kW
l/h
l/h
kPa
l/h
kPa
W/W
W/W
A
A
A
n°/n°
ø gas M
ø gas M
l
kW
A
kPa
dB(A)
dB(A)
mm
mm
mm
kg
reverberant test chamber with reverberation
7 °C
time Tr = 0.5 sec.
NOTE
5°C
(1) The consumption of water at 16 °C refers
to a unit with pressure switch valve, which is
015
020
5,3
6,9
1,7
2,0
910
1. 1 90
1. 1 90
1.500
11,4
17,5
320
400
1,0
1,5
3, 1 2
3,45
4,03
4,77
230V ~ - 50 Hz
8,6
9,4
13
15
48
61
1/Rotary
1/Scroll
1
1
1"
1"
1
1
1"
1"
23
23
0,095
0, 1 65
0,42
0,8
54
63
56,0
56,5
47,5
48,0
625
625
404
404
504
504
85
96
appropriately calibrated.
025
030
8,2
9,7
2,3
2,7
1.410
1.670
1.780
2. 1 00
13,4
11,7
470
560
1,2
1,6
3,57
3,59
4,92
4,81
11, 1
13,0
18
24
76
100
1/Scroll
1/Scroll
1
1
1"
1"
1
1
1"
1"
23
23
0, 1 8
0,2
0,8
0,8
61
59
57,0
57,5
48,5
49,0
625
625
404
404
504
504
98
100
9

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Venice-h

Tabla de contenido