DL5
gate closing M1 (red)
DL6
automatic closing indicator (red)
DL7
photocell contact (NC) (red)
DL8
sensor contact (NC) (red)
DL9
STOP button (NC) (red)
DL10 radio code program (green)
FUSES
Fuse 1 T 8A MOTOR PROTECTION FUSE
F1 T 2A
TRANSFORMER PROTECTION FUSE (on the outside of the T2 24V board)
C
- MOTOR ROTATIONAL DIRECTION CONTROL
1 - Set DIP 1 to ON => LED DL1 starts flashing.
2 - Press and hold the PROG button. (movement is now manually controlled - open-stop-close-stop-open - etc.) =>
GREEN LEDS DL2 and DL4 are lit and the gate panels open with a fixed lag of 2 sec. If they close instead of
open, release the button and reverse the two wires on the motor used.
3 - After opening release the PROG button and calibrate the mechanical opening stops (on the operator).
4 - Press and hold the PROG button => RED LEDs DL3 and DL5 turn on and the gate panels close with a time
lag of 2 sec.
5 - Continue to hold the PROG button until the gate is completely closed.
6 - Leave the two doors completely closed to set the timer.
7 - Reset DIP1 to OFF => LED DL1 turns off, signaling exit from control.
N.B.: During this check the stop, the photocells and the sensors are not active.
D
- SETTING THE TIMER FOR 2 MOTORS (#) WITH POWER SENSOR ACTIVATED (DIP 7 ON)
WHILE SETTING THE TIMER THE POWER SENSOR IS CONTINUOUSLY ACTIVATED.
1 - The gate must be completely closed.
2 - Set DIP 2 to ON => LED DL1 will blink rapidly.
3 - Press the PROG button. => M1 opens.
4 - When the mechanical opening stop is reached, the AUTOMATIC POWER SENSOR stops M1 (memorizing the
time and the power) => At the same time M2 is triggered to open.
5 - When the mechanical opening stop is reached, the AUTOMATIC POWER SENSOR stops M2 (memorizing the
time and the power).
6 - Press the PROG button. => M2 closes.
7 - Press the PROG button. => M1 closes and sets the lag time between M2 and M1. At the same time LED DL1
stops flashing indicating exit from the programming procedure.
Safety and other gate commands now operate normally (inversions, stop, alarms, etc.).
8 - The gate panels will close in high-speed mode (depending on how you set the RUN trimmer) and near total closure
in the slow mode (depending on how you set the LOW-SPEED trimmer).
9 - Upon closing the power sensors stop the gate.
10 - AFTER PROGRAMMING RESET DIP 2 TO OFF.
D
- SETTING THE TIME FOR ONE MOTOR (M1) (#) WITH POWER SENSOR ACTIVATED (DIP 7 ON)
CAUTION: FOR ONE MOTOR CONTROL DIP 13 MUST BE POSITIONED TO ON; DURING PROGRAMMING THE
POWER SENSOR IS CONTINUOUSLY ACTIVE.
The gate must be completely closed.
1 - Set DIP 2 to ON => LED DL1 will blink rapidly.
2 - Press the PROG button. => M1 opens.
When the mechanical opening stop is reached, the AUTOMATIC POWER SENSOR stops M1 (memorizing the
time and the power).
3 - Press the PROG button. => M1 closes.
At the same time LED DL1 stops flashing indicating exit from programming. Safety and other gate commands
now operate normally (inversions, stop, alarms, etc.).
Upon closing the power sensor stops the gate.
4 - AFTER PROGRAMMING RESET DIP 2 TO OFF.
(#) DURING PROGRAMMING THE SAFETY DEVICES ARE ACTIVE AND STOP THE PROGRAMMING
PROCEDURE (LED DL1 FROM FLASHING BECOMES CONSTANT). TO REPEAT PROGRAMMING SET DIP 2
TO OFF, CLOSE THE GATE USING THE PROCEDURE "MOTOR ROTATIONAL DIRECTION CONTROL" AND
REPEAT THE DESIRED PROGRAMMING PROCEDURE.
D
- SETTING THE TIME FOR 2 MOTORS (#) WITH TIME OPERATION (DIP 7 OFF)
1 - The gate must be completely closed.
2 - Set DIP 2 to ON => LED DL1 will blink rapidly.
3 - Press the PROG button. => M1 opens.
4 - When the mechanical opening stop is reached, wait a second then press the PROG button => M1 stops and
M2 opens.
5 - When the mechanical opening stop is reached => wait 1 second and press the PROG button => M2 stops.
6 - Press the PROG button => M2 closes.
7 - Press the PROG button => M1 closes setting the time lag between M2 and M1.
At the same time LED DL1 stops flashing indicating exit from the programming procedure.
Safety and other gate commands now operate normally (inversions, stop, alarms, etc.).
8 - After the set amount of time, the gate will stop.
9 - AT THE END OF PROGRAMMING RESET DIP 2 TO OFF.
NOTE: The slowdown is automatically determined by the control board during the time setting phase and is activated
at about 50 to 60 cm before reaching the mechanical opening or closing limit.
D
- SETTING THE TIME FOR 1 MOTOR (#) WITH TIME OPERATION (DIP 7 OFF)
CAUTION: FOR ONE MOTOR CONTROL DIP 13 MUST SET TO ON
1 - The gate must be completely closed.
2 - Set micro-switch DIP 2 to ON => LED DL1 will blink rapidly.
3 - Press the PROG button => M1 opens.
4 - When the mechanical opening stop is reached, wait a second then press the PROG button => M1 stops.
5 - Press the PROG button => M1 closes.
At the same time LED DL1 stops flashing indicating exit from the programming procedure.
Safety and other gate commands now operate normally (inversions, stop, alarms, etc.).
6 - After the set amount of time, the gate will stop.
7 - AT THE END OF PROGRAMMING RESET DIP 2 TO OFF.
D
- SETTING PEDESTRIAN OPENING TIMES (#) BOTH FOR TIME AND POWER SENSOR OPERATION
With gate closed:
1 - First set DIP2 to ON (LED DL1 flashes quickly) and then DIP1 to ON ( LED DL1 flashes slowly).
2 - Push the pedestrian button (COM-PED.BUTT) => M1 opens.
3 - Push the pedestrian button to stop movement (thereby setting M1 opening).
4 - Push the pedestrian button to start closing.
5 - Upon closing reset DIP 1 and 2 to OFF.
(#) DURING PROGRAMMING THE SAFETY DEVICES ARE ACTIVE AND STOP THE PROGRAMMING
PROCEDURE (LED DL1 FROM FLASHING BECOMES CONSTANT).
TO REPEAT PROGRAMMING SET DIP 2 TO OFF, CLOSE THE GATE USING THE PROCEDURE "MOTOR
ROTATIONAL DIRECTION CONTROL" AND REPEAT THE DESIRED PROGRAMMING PROCEDURE.
E
- RADIO CODE PROGRAMMING FOR TOTAL OPENING
(UP TO 62 CODES - CRX MODELS ONLY)
Programming can be done only when the gate is stationary.
1 - First set DIP 1 to ON and then DIP 2 to ON.
2 - The red LED DL1 flashes ON every 1 sec. and OFF for 10 seconds.
3 - Press the remote control button (usually channel A) within the allotted 10 seconds. If the remote is memorized
properly LED DL10 (green) blinks.
4 - The programming time for codes is automatically renewed in order to memorize the next remote control.
5 - To finish programming, wait 10 seconds, or press the PROG button briefly. The red LED DL1 stops flashing.
6 - Reset DIP 1 to OFF and DIP 2 to OFF.
7 - End of procedure.
CANCELLATION OF ALL RADIO CODES FOR TOTAL OPENING
Cancellations can only be performed when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The red LED DL1 flashes ON every 1 second and OFF for 10 seconds.
3 - Press and hold the PROG button for 5 seconds. Memory cancellation is indicated by two flashes of green LED
DL10.
4 - The red LED DL1 remains active and you can add new codes as shown above.
5 - Reset DIP 1 to OFF and DIP 2 to OFF.
6 - End of procedure.
INDICATOR MEMORY FULL OF RADIO CODES FOR TOTAL OPENING
Indication only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The green LED DL10 flashes 6 times when the memory is full (62 codes).
3 - LED DL1 will then remain active for 10 seconds enabling possible cancellation of codes.
4 - Reset DIP 1 to OFF and DIP 2 to OFF.
5 - End of procedure.
F
- PROGRAMMING PEDESTRIAN OPENING RADIO CODES
(UP TO 62 CODES - CRX MODELS ONLY)
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - The red led DL1 flashes ON for 1 second and OFF for 1 second for 10 seconds.
3 - Press the remote control button (usually channel B) within the allotted 10 seconds. If the remote is properly
memorized LED DL10 (green) blinks.
4 - The programming time for codes is automatically renewed in order to memorize the next remote control.
5 - To finish programming wait 10 seconds, or press the PROG button briefly. The red LED DL1 stops flashing.
6 - Reset DIP 1 to OFF and DIP 3 to OFF.
NOTE: If LED DL1 CONTINUES BLINKING QUICKLY IT MEANS THAT DIP 1 IS STILL SET TO ON AND
THAT ANY OPERATION IS REFUSED.
7 - End of procedure.
CANCELLATION PROCEDURE FOR ALL PEDESTRIAN OPENING RADIO CODES
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - The red LED DL1 flashes ON for 1 second and OFF for 1 second for 10 seconds.
3 - Press and hold the PROG button for 5 seconds. Memory cancellation is indicated by two flashes of green LED
DL10.
4 - The red LED DL1 remains active and you can add new codes as shown above.
5 - Reset DIP 1 to OFF and DIP 3 to OFF.
6 - End of procedure.
INDICATION MEMORY FULL OF PEDESTRIAN OPENING RADIO CODES
Indication only when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - The green LED DL10 flashes 6 times when the memory is full (62 codes).
3 - The LED DL1 will then remain active for 10 seconds enabling possible cancellation of codes.
4 - Set DIP 1 to OFF and DIP 3 to OFF.
5 - End of procedure.
C
ONTROL ACCESSORIES OPERATION
STEP-BY-STEP BUTTON (COM-K BUTTON)
If DIP 6 OFF => It cyclically performs the commands open-stop-close-stop-open etc.
If DIP 6 ON => Opens the gate when closed. There is no effect if activated while opening. If activated when gate is
open, the gate closes. If activated while closing, the gate reopens.
OPEN BUTTON (COM-OPEN)
The button controls the opening movement when the gate is stationary. If activated while closing, it reopens the gate.
G
B