Quick Installation
Optional Hardwire Input
(Select models only. Proceed to Step
system.)
Hardwire Warnings
• Wiring must be performed by a qualified electrician.
• A readily visible and adequate disconnect device must be provided.
• Make sure that your equipment is properly grounded.
• When making wiring connections, observe local/national cable connection regulations
at all times. Ensure that cables are fitted with cable sleeves and secured by connector
clamps.
• Using cables of improper size may damage your equipment and cause fire hazards.
Choose appropriate cabling and protection circuits to make wiring connections.
(Ground conductors must be the same size and type as power conductors.)
• Overcurrent protection should be provided per local/national electrical codes.
3A
Select models have an optional hardwire
input that can be connected by a qualified
electrician. While the UPS system is turned
OFF and unplugged, remove the input power
cord
, the input power cord panel
A
the adjacent wiring access panel
3B
The input terminal block should be wired
directly to a dedicated AC supply circuit rated
in accordance with the specifications listed
on the UPS system nameplate. The hardwire
input panel
the input power cord panel. (Note: The
hardwire input panel has a larger cutout that
accommodates conduit.) After threading
user-supplied input wiring through user-
supplied conduit, insert the conduit through
the hardwire input panel and connect the
input wiring to the input terminal block. The
terminals are labeled " " for ground, "N" for
neutral and "H" for hot. Connect the input
hot wire to the input hot terminal
the input neutral wire to the input neutral
terminal
the ground terminal
3C
After connecting the input wiring to the
terminal block, secure the wiring access
panel
C
14-12-044-932757.indb 7
continued
will be visible after you remove
D
. Connect the input ground wire to
F
.
G
and the hardwire input panel
unless you plan to hardwire the UPS
4
and
B
.
C
3A
E
F
G
3B
. Connect
E
3C
.
D
7
C
B
A
D
INPUT
H
N
C
D
12/16/2014 5:11:04 PM