System Setup - Briggs & Stratton Dual 200 Amp Manual De Instrucciones

Ocultar thumbs Ver también para Dual 200 Amp:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

System Setup

You must perform the following before operating the system:
• If generator is installed in an area regularly subjected to
temperatures below 40°F (4°C), select a 50 second warm up
time by moving jumper JP2 (C) installed on transfer switch
control board from '20' position to '50' position.
• Set the DPSW1 (A) and DPSW2 (B) dipswitches on the
transfer switch control board to match the kW rating of the
standby generator, as described in Setting Dipswitches.
Setting Dipswitches
Dipswitches are used to adjust control board operation based
on generator capacity. DPSW1 and DPSW2 switches are set to
correspond to total system kW rating. Dipswitch DPSW1 (A) has
units of 1,000 watts; Dipswitch DPSW2 (B) has units of
10,000 watts.
Set dipswitches with utility and generator power removed from
the transfer switch to ensure proper control system operation.
If dipswitches are set when power is present at transfer switch,
a power reset needs to be performed before the new dipswitch
settings will take effect. Power reset is when all power is removed
from the transfer switch and then reintroduced after 30 seconds.
NOTICE Transfer switch fault message will occur on standby
generator control board if dipswitches are not properly established
as noted above.
To properly establish the dipswitches, make sure that only one
dipswitch is set to "ON" position for DPSW1 and one dipswitch for
DPSW2. For example a 20kW generator, set DPSW2 dipswitch 20
to "ON" position and DPSW1 dipswitch 0 to "ON" position.
20,000 plus 0 equal 20,000 watts.
14
NOTICE Use extreme caution when setting dipswitches or
damage to control board will result.
• Use a pencil or small piece of plastic to set the dipswitch.
• NEVER use a screwdriver or any type of metal object to set
dipswitches.
The "On" position for the dipswitches is the switch number ON
THE TRANSFER SWITCH CONTROL BOARD, not on the switch. For
example, for an 18,000 watt generator, set DPSW2 dipswitch 10 to
"On" position. Set DPSW1 dipswitch 8 to "On" position. 10,000 plus
8000 equals 18,000 watts. Set only one switch to "On" position
A
on DPSW1 and DPSW2.
Refer to following chart for proper switch selection(s).
B
C
NOTICE Air density is less at high altitudes, resulting in less
available engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 meters) above sea level and 1% for each 10°
F (5.6°C) above 77°F (25°C). Generators located in these conditions
must have the transfer switch programmed appropriately for this
power decrease.
kW Rating
DPSW
A
of
#1 "ON"
Generator
Position
7kW
7
8kW
8
9kW
9
10kW*
0
11kW*
1
12kW
2
13kW*
3
14kW
4
15kW
5
16kW
6
17kW
7
18kW
8
19kW
9
20kW
0
30kW
0
45kW
5
48kW
8
50kW
0
60kW
0
* For generators with a rating that includes 500 Watts, round down to
next lowest rating
(example: 13.5 kW set to 13kW)
BRIGGSandSTRATTON.COM
DPSW
B
#2 "ON"
Position
0
0
0
10
10
10
10
10
10
10
10
10
10
20
30
40
40
50
60
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Split 400 amp

Tabla de contenido