. K. reduction. coefficient. for. liquid.
fuels:.0.024
. P. boiler.input.in.Kcal/h
. H. height. of. the. flue. in. meters.
measured. from. the. flame. axis.
to.the.flue.outlet.into.the.atmos-
phere.. When. . dimensioning. the.
flue,. the. effective. height. of. the.
flue. in. meters. must. be. consid-
ered,.measured.from.the.flame.
axis. to. the. top. of. the. flue,. re-
duced.by:
. .
–. 0.50.m.for.each.change.of.di-
rection. of. the. connection. un-
ion.between.boiler.and.flue;
. .
–. 1.00.for.each.horizontal.metre.
of.the.union.itself.
KEY
1..
Stainless.steel.coaxial.flue.L..886.code.8096220
2.a.. Stainless.steel.extension.L..1000.code.8096121
2.b.. Stainless.steel.extension.L..500.code.8096120
3.a.. 90°.stainless.steel.curve.code.8095820
3.b.. 45°.stainless.steel.curve.code.8095920
4..
Stainless.steel.vertical.condensation.recovery.L..135.code.8092820
5..
Tile.with.hinge.code.8091300
6..
Roof.outlet.terminal.L..1063.code.8091203
7.
Kit.code.8098810
TABLE A
.
90°.stainless.steel.curve.
45°.stainless.steel.curve.
Stainless.steel.extension.L..1000.
Stainless.steel.extension.L..500.
Roof.outlet.terminal.L..1063.
Stainless.steel.coaxial.flue.L..886.
Stainless.steel.vertical.condensation.recovery.L..135.
1
WARNING:
Our.boilers.are.the.B
need.any.particular.connections.other.
than. the. one. to. the. flue. as. described.
above.
2.3.2
Smoke exhaust with
ø 80/125 coaxial flue
(type C) (fig. 6)
The boiler converted into type C with
the kit code 8101594. are. set. to. be.
connected.to.ø.80/125..stainless.steel.
coaxial. flues. that. can. be. adjusted. to.
the. most. suitable. direction. for. room.
requirements.(fig..6)...
The maximum acceptable length of
Load.loss.(mt)
3
2
7
3
ø 80/125
The maximum acceptable length of the flue must not be over 7.0 equivalent meters.
Always use the condensation recovery (4) in outlets with vertical exhaust.
.type.and.do.not.
23
6
1,80
0,90
1,00
0,50
1,00
0,70
0,70
5
2
4
3
the flue must not be over 7.0 equiva-
lent meters.
Load losses in meters for each single
accessory to be used in the exhaust
configuration are indicated in Table
A.
Only. use. original. SIME. accessories.
and. make. sure. that. connections. are.
correct.as.indicated.in.the.instructions.
supplied.with.the.accessories.
2.4
FUEL ADDUCTION
(figg. 7 - 7/a)
The. fuel. can. be. fed. into. the. thermal.
group. sideways,. the. ducts. must. be.
7
Fig..6
63