7. Funciones técnicas de seguridad
Condiciones del sistema
Banco de datos para rangos de fallo
Tipo de sistema
Norma empleada
Factor beta
7.1. Desconexión segura
Temperatura ambiente
MTTF [años] Mean time to failure
Tiempo de desconexión [ms]
λsd [FIT] safe, detectable
λsu [FIT] safe, undetectable
λdd [FIT] dangerous, detectable
λdu [FIT] dangerous, undetectable
SFF [%] Safe Failure Fraction
DCS [%] Diagnostic coverage safe
DC [%] Diagnostic coverage
PFD Probability of Failure on Demand
PFH Probability of a dangerous
failure per hour
Nivel de seguridad
7.2. Guardamotor
Temperatura ambiente
Tiempo de desconexión [ms]
λsd [FIT] safe, detectable
λsu [FIT] safe, undetectable
λdd [FIT] dangerous, detectable
λdu [FIT] dangerous, undetectable
SFF [%] Safe Failure Fraction
DCS [%] Diagnostic coverage safe
DC [%] Diagnostic coverage
PFD Probability of Failure on Demand
Nivel de seguridad
50
SN 29500
tipo B, compuesto de sistemas subordinados
IEC 61508
1 %
ELR W3-24DC/500AC-...
40 °C
45,6
40
666
947
215
2,5
99,86
50,56
98,86
compárese diagrama 7.3.
2,48 x 10
según
IEC 61508-1: SIL 3
ISO 13849-1: PL e
EN 954-1:
ELR W3-24DC/500AC-...
40 °C
645
866
238
17
99
42,6
93,3
compárese diagrama 7.4.
según
IEC 61508-1: SIL 2
60 °C
23,0
1561
1643
446
5,01
99,9
48,73
99
-9
-9
5,01 x 10
categoría 3
60 °C
según Class 10A, IEC 60947
1487
1408
488
37
98,9
51,36
93
ELR W3-230AC/500AC-...
40 °C
60 °C
46,0
23,0
80
641
1217
879
1814
399
896
4,43
9,67
99,77
99,75
42,17
40,2
98,9
98,93
compárese diagrama 7.3.
-9
4,43 x 10
9,67 x 10
ELR W3-230AC/500AC-...
40 °C
60 °C
647
1212
812
1622
413
915
17
37
99,1
99
44,4
42,8
96
96,1
compárese diagrama 7.4.
-9