Hazardous Area
Zone 2 and 22
Terminal 1,2
Ex nA & ec
Vmax= 37 VDC
Vmax= 30 VDC
Terminal 3,4,5,6,7,8,9
Ex nA & Ex ec
Vmax = 7.2VDC
General installation instructions
If the enclosure is made of non-metallic materials or of painted metal, electrostatic
charging shall be avoided. For an ambient temperature ≥ 60ºC, heat resistant cables
shall be used with a rating of at least 20 K above the ambient temperature.
The enclosure shall be suitable for the application and correctly installed.
The maximum surface temperature of the outer enclosure is 20 K hotter than the
maximum ambient temperature.
The distance between terminals, inclusive the wires bare part, shall be at least 3 mm
separated from any earthed metal.
'TEST' connection, may only be applied when the area is safe, or if supply / output
circuit and the applied current meter are intrinsically safe.
34
9
8
7
6
5
5431A
4
5434A
5435A
3
5437A
Terminal 1,2
Terminal 1,2
Ex ic
Ex ic
Ui = 37 VDC
Ui = 48 VDC
Li = 0 μH
Pi = 851 mW
Ci = 1.0 nF
Li = 0 μH
Ci = 1.0 nF
Ui = 30 VDC
Li = 0 μH
Ci = 1.0 nF
Terminal 3,4,5,6,7,8,9
Ex ic
Uo: 7.2 VDC
Io: 12.9 mA
Po: 23.3 mW
Lo: 200 mH
Co: 13.5μF
Unclassified Area
Power
+
1
Supply
‐
2
or
Zone 2
barrier
Temperature Range
T4: -50 ≤ Ta ≤ 85ºC
T5: -50 ≤ Ta ≤ 70ºC
T6: -50 ≤ Ta ≤ 55ºC
T4: -50 ≤ Ta ≤ 85ºC
T5: -50 ≤ Ta ≤ 75ºC
T6: -50 ≤ Ta ≤ 60ºC
5437V101-ES