4.8.2
Main connection diagrams
4.8.2.1 Three-phase alternators – Multi-voltage
Star Series (access to neutral)
L - L
380 - 415
L - N
220 - 240
60Hz
190 - 207
(Sensing)
L - L
L - N
50Hz
E1 - E3/4
(Sensing)
ATTENTION
The alternator is supplied with the voltage regulator (AVR) connected to operate at the alternator rated
characteristics;
In case of maintenance or modification of the alternator wiring connections, connect correctly the cables E1,
E3/4 and 3 on the AVR, as follows:
- The cables E1 and E3/4 refers to AVR sensing voltage.
- The cables 3 and E3/4 refers to AVR power supply.
In alternators with 12 terminals, always connect the alternator cables E1 and E3/4 on the AVR terminals E1
and E3/4, regardless of connection type or alternator rated voltage. In these cases, the AVR terminal E2 should
not be used.
12638144
Installation, operation and maintenance manual – Synchronous Alternator – AG10 line - Horizontal l 29
Star Parallel (access to neutral)
440 - 480
190-208
254 - 277
110-120
220 - 240
190-208
380 – 400
220 – 230
190 – 200
8 pins
12 pins
VOLTAGE ( V )
220 – 240
127 – 139
220 – 240
190 – 200
110 – 115
190 – 200
8 pins
12 pins
www.weg.net
Delta Series
220 – 240
–
220 – 240
200 – 220
–
200 – 220
8 pins
12 pins