Limit Value (Alarm) Monitoring - Kübler CODIX 565 Manual Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

9.6

Limit Value (Alarm) Monitoring

Page 16
Menu Alarm Output 1
Select operating mode
OFF
Automatic operation
Memory latch operation
- not with band limitation
Select source value for Alarm
output 1
Current measured value
Totaliser
Select Output triggering
With incrementing measuring
signal
With decrementing measuring
signal
Band limitation
Select Alarm status
With alarm: output active
With alarm: output inactive
Select on-hysteresis
Input range
0 ... +9999 and DP
Select off-hysteresis
- only with auto operation
Input range
0 ... +9999 and DP
Select on-delay
Input range 0.0 ... 99.9 [sec]
Select off-delay
- only with auto operation
Input range 0.0 ... 99.9 [sec]
Menu Alarm Output 2
Select operating mode
OFF
Automatic operation
Memory latch operation
Select source value for Alarm
output 2
Current measured value
Totaliser
Select Output triggering
With incrementing measuring
signal
With decrementing measuring
signal
Band limitation
Select Alarm status
With alarm: output active
With alarm: output inactive
Select on-hysteresis
Input range
0 ... +9999 and DP
Select off-hysteresis
- only with auto operation
Input range
0 ... +9999 and DP
Select on-delay
Input range 0.0 ... 99.9 [sec]
Select off-delay
- only with auto operation
Input range 0.0 ... 99.9 [sec]
ON switching point = limit value + ON hysteresis
OFF switching point = limit value – OFF hysteresis
ON switching point = limit value – ON hysteresis
OFF switching point = limit value + OFF hysteresis
An alarm is triggered, if the measured value falls
outside a defined range (Band).
Upper switching point = limit value + ON hysteresis
Lower switching point = limit value – OFF
hysteresis
An alarm causes the output to become active
(Relay energised, LED ON)
An alarm causes the output to become inactive
(Relay not energised, LED OFF)
In memory latch operation the status of the outputs
is stored in the event of a Power OFF condition
and then immediately restored at the next Power
ON.
In auto operation the status of the outputs is not
saved in the event of a Power OFF condition. At
the next Power ON the limit values are not
processed until after the expiration of the start
delay (PW.DELY).